ATEX – 'Ex i' type of protection
Ex marking
Marking
Type Examination Test Certificate
Type
Standards
Temperature Data
Device group II 2 G
Temperature class
T4
T5
T6
*
*
When using the plug−in module for 'Digital Feedback' in Temperature
Class T6, the maximum permissible ambient temperature range is
−40 to 35 °C (−40 to 95 °F).
Electrical data for ia / ib / ic for groups IIB / IIC
With the intrinsically safe Ex i IIC type of ignition protection, only
for connection to a certified FISCO power supply unit or a
barrier, i.e., a power supply unit with maximum values according
to the following table:
Current circuit (terminal)
Signal circuit
(+11 / −12)
With the intrinsically safe Ex i IIC type of protection, only for
connection to a certified intrinsically safe circuit with maximum
values:
Current circuit (terminal)
Mechanical digital feedback
For maximum values, see EC type examination
(+51 / −52)
(+41 / −42)
II 2 G Ex ia IIC T6 or T4 Gb
II 2 G Ex ib IIC T6 or T4 Gb
II 3 G Ex ic IIC T6 or T4 Gc
TÜV 02 ATEX 1831 X
TZIDC-210
EN 60079-0
EN 60079-11
Ambient temperature Ta
−40 to 85 °C
−40 to 50 °C
−40 to 40 °C *
Electrical information (maximum values)
U
= 24 V
i
I
= 250 mA
L
i
P
= 1.2 W
Characteristic curve =
i
Electrical information (maximum values)
certificate number
PTB 00 ATEX 2049 X
Special conditions
Before final installation, the operator needs to decide on the
use of the device, either
A) as a device with 'Ex i' intrinsically safe type of protection
or
B) as a device with 'Ex d' type of protection
and permanently mark the selected type of use on the name
plate. Specific conditions of the surrounding environment,
such as chemical corrosion, must be taken into account when
affixing the permanent mark. Only the manufacturer must
change the selected type of use following a re-examination
Variants that, according to declarations, also meet the
requirements for the 'flameproof enclosure' type of
protection may no longer be used as 'intrinsically safe' if they
have been previously used as a flameproof type of protection
IECEx – 'Ex d' type of protection
Ex marking
Marking
Type Examination Test Certificate
Type
Standards
Temperature Data
Temperature class
T4
T5
T6
C
< 5 nF
i
< 10 μH
i
linear
13
Ex d IIC T4/T5/T6
IECEx BVS 07.0030X, Issue No.: 0
TZIDC-200
IEC 60079-0
IEC 60079-1
Ambient temperature Ta
−40 to 85 °C
−40 to 80 °C
−40 to 65 °C