Iecex - 'Ex D' Type Of Protection - ABB TZIDC-200 Operating Instruction

Digital positioner
Hide thumbs Also See for TZIDC-200:
Table of Contents

Advertisement

10
TZIDC-200, TZIDC-210, TZIDC-220 DIGITAL POSITIONER | 42/18-85-EN REV. E
... 2 Use in potentially explosive atmospheres
... TZIDC-200 – Ex relevant specification
Current circuit (terminal)
Plug-in module for analog
position feedback
(+31 / −32)
Local communication
interface (LCI)
Special conditions
Before final installation, the operator needs to decide on the
use of the device, either
A) as a device with 'Ex i' intrinsically safe type of protection
or
B) as a device with 'Ex d' type of protection
and permanently mark the selected type of use on the name
plate. Specific conditions of the surrounding environment,
such as chemical corrosion, must be taken into account when
affixing the permanent mark. Only the manufacturer must
change the selected type of use following a re-examination
Variants that, according to declarations, also meet the
requirements for the 'flameproof enclosure' type of
protection may no longer be used as 'intrinsically safe' if they
have been previously used as a flameproof type of protection
The local communication interface (LCI) may only be
operated at U
≤ 30 V DC outside the hazardous area.
m
Electrical information (maximum values)
U
= 30 V
i
I
= 320 mA
L
= negligibly small
i
i
P
= 1.1 W
i
Only for connection to a programming device
outside the hazardous area (see special
IECEx – 'Ex d' type of protection
Ex marking
C
= 6.6 nF
Marking
i
Type Examination Test Certificate
Type
Temperature Data
conditions).
Temperature class
T4
T5
T6
Electrical Data
Voltage
Current
Pneumatic data
Supply pressure
Special conditions
The positioner is designed for a maximum permissible
ambient temperature range of 40 to 85 °C
Variants that, according to declarations, also meet the
requirements for the 'intrinsically safe' type of protection
may no longer be used as 'intrinsically safe' if they have been
previously used as a flameproof type of protection
If the positioner is operated at an ambient temperature
above 60 °C (140 °F) or below −20 °C (−4 °F), make sure to
use cable entries and lines suited for an operating
temperature corresponding to the maximum ambient
temperature increased by 10 K or corresponding to the
minimum ambient temperature, respectively.
Ex d IIC T4/T5/T6
IECEx BVS 07.0030X
TZIDC-200
Ambient temperature Ta
−40 to 85 °C
−40 to 80 °C
−40 to 65 °C
≤ 30 V AC/DC
≤ 20 mA
Standard version
≤ 6 bar
Marine version
≤ 5.5 bar

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tzidc-210Tzidc-220

Table of Contents