Installation; Orientation - UTC Fire and Security DET-TRONICS FlexVu UD10 Instructions Manual

Explosion-proof universal display unit
Table of Contents

Advertisement

NOTES
1. SHIELDED SENSOR WIRING CABLE REQUIRED.
2. GROUND SENSOR WIRE SHIELD AT TRANSMITTER END ONLY.
3. SHIELDS SHOULD BE STRIPPED BACK WITHIN JUNCTION BOXES.
4. P/N 102883-001 TERMINAL CONNECTOR REQUIRED FOR SENSOR CONNECTION
4.
(PROVIDED WITH SENSOR TERMINATION BOX).
5. HOUSINGS MUST BE ELECTRICALLY CONNECTED TO EARTH GROUND.
UD10 Wired to Model 505 Transmitter/CGS Sensor Using Sensor Separation Termination box

instAllAtion

Refer to the Model 505 Instruction Manual (number
95-8472) for complete information regarding proper
installation of the Model 505 with combustible gas
sensor.
4.3
Sensor Connector
Output Loop
Connector
4-20 mA +
P1-3
P1-2
4-20 mA –
SHIELD
P1-1
P1
J2
COM
J2-3
J2-2
RS485 A
J2-1
RS485 B
MODBUS
Connector
Power Supply Connector
CONNECT KEYED SENSOR
PLUG TO PIN CONNECTOR
UD10
DISPLAY UNIT
J3
J4-1
HIGH ALARM COM
HIGH ALARM NC
J4-2
HIGH ALARM NO
J4-3
AUX ALARM COM
J4-4
J4-5
AUX ALARM NC
J4-6
AUX ALARM NO
J4-7
LOW ALARM COM
J4-8
LOW ALARM NC
LOW ALARM NO
J4-9
FAULT COM
J4-10
FAULT NC
J4-11
FAULT NO
J4-12
J4
P2

orientAtion

The Model 505/CGS must be mounted with the CGS
sensor opening pointing down.
H-2
MODEL 505 TRANSMITTER
BLK
WHT
RED
CGS
SENSOR
B2475
95-8618