OPERATiNG VOLTAGE—
24 Vdc nominal, operating range is 18 to 30 Vdc.
OPERATiNG POWER—
7 watts maximum.
Heater off:
2 watts @ 24 Vdc with alarm relays off and
4 mA output.
Heater off:
4 watts @ 24 Vdc with alarm relays on and
20 mA output.
Heater on:
5.5 watts @ 24 Vdc with alarm relays off
and 4 mA output.
Heater on:
7 watts @ 24 Vdc with alarm relays on and
20 mA output.
Heater function is not user configurable. Heater
turns on when the internal temperature drops
below –10°C.
Appropriate relays will be activated when a fault
or alarm occurs.
CURRENT OUTPUT—
Linear isolated 4-20 mA output with HART.
3.8 mA indicates calibrate mode.
3.6 mA or less indicates a fault condition.
Maximum loop resistance is 600 ohms at 18 to 30 Vdc.
CURRENT OUTPUT RESPONSE TiME—
Toxic gas mode:
Combustible gas mode:
Combustible gas - open path mode: T90 = <4 seconds.
CURRENT OUTPUT ACCURACy—
Toxic gas mode:
Combustible gas mode:
Combustible gas - open path mode: ≤0.01 LFL/M.
RELAy CONTACTS—
Three Alarm Relays: Form C, 5 amperes at 30 Vdc.
Selectable latching or non-latching.
Refer to Table 1 for range and
default settings.
WarnIng
When in non-latching mode, the control device
must latch the alarm output.
One Fault Relay:
Form C, 5 amperes at 30 Vdc.
Normally energized for no fault
condition with power applied.
RELAy RESPONSE TiME—
≤ 2 seconds.
4.3
noTe
noTe
T90 = ≤5 seconds.
T90 = <4 seconds.
<1% error.
<1% error.
WiRiNG TERMiNALS—
14 to 18 AWG wire can be used.
OPERATiNG TEMPERATURE—
–55°C to +75°C.
STORAGE TEMPERATURE—
–55°C to +75°C.
HUMiDiTy RANGE—
5 to 95% RH (Det-Tronics verified).
CERTiFiCATiON—
FM:
Class I, Div. 1, Groups B, C & D;
Class I, Div. 2, Groups B, C & D (T4);
Class I, Zone 1/2 AEx d IIC T6;
Class II/III, Div. 1/2, Groups E, F & G.
F M
T amb –55°C to +75°C
APPROVED
NEMA/Type 4x, IP66
Conduit seal not required.
Performance verified in accordance with:
ANSI/ISA-92.00.01
ANSI/ISA-92.02.01
FM 6341 (Draft)
ANSI/ISA-12.13.01
ANSI/ISA-12.13.04/FM 6325
FM 6310/6320
CSA:
CSA 08 2029512.
Class I, Div. 1, Groups B, C & D;
Class I, Div. 2, Groups B, C & D (T4);
Class II/III, Div. 1/2, Groups E, F & G.
F M
®
(T amb = –55°C to +75°C)
APPROVED
Type 4x
Conduit seal not required.
Performance verified in accordance with:
CSA C22.2 #152.
16
®
This approval does not include or imply
approval of gas detector heads or other
apparatus to which the subject instrument
may be connected. In order to maintain a
Factory Mutual Research approved system,
the measurement input signal to which
this instrument is connected must also be
approved by Factory Mutual Research.