UTC Fire and Security DET-TRONICS FlexVu UD10 Instructions Manual page 17

Explosion-proof universal display unit
Table of Contents

Advertisement

Device Faults
EE Fault
Fault in non-volatile memory
Sensor signal level is outside the range of the AD
Ref ADC Sat
converter
Sensor signal level is outside the range of the AD
Active ADC Sat
converter
24V Fault
Problem in 24 volt power supply or power wiring
Flash CRC Fault
Memory fault
RAM Fault
Fault in volatile memory
Low Voltage
Power supply voltage outside of limits
Temp Fault
Temperature sensor fault
Software Fault
internal software fault
EE Safety Fault
internal configuration fault
Gas Under Range
Sensor signal has drifted negative
Sensor Mismatch
Wrong sensor type is installed
ADC CNTR Fault
internal hardware fault
3V Fault
3 volt internal power supply out of tolerance
Comm Fault
Communication fault
GEN Fault
Unspecified fault
12V Fault
12 volt internal power supply out of tolerance
5V Fault
5 volt internal power supply out of tolerance
4.3
Table 4—Troubleshooting Guide - Device Faults, Continued
Description
15
Recommended Action
Power may have been interrupted while the device
was updating its internal data logs. Recycle
power.
Return to factory.
Return to factory.
Check power wiring and output voltage of power
supply.
Return to factory.
Return to factory.
Check power supply voltage.
Return to factory.
Return to factory.
Return to factory.
Return to factory.
Device may have been calibrated with background
gas present. Recalibrate the detector. Purge with
clean air if needed.
Sensor type must match configuration. Change
sensor or configuration.
Return to factory.
Return to factory.
Check detector wiring and power supply.
Verify correct power wiring and supply voltage.
Consult the factory.
Return to factory.
Return to factory.
95-8618