orientAtion
OPECL modules must be affixed to a solid, non-vibrating
structure capable of supporting a minimum of 100 lbs (46
kg), located within the system's rated separation distance.
See examples below.
In all cases, the maximum movement of the supporting
structure under all anticipated operating conditions must
be no more than ±0.25 degrees. When using a vertical
post, the post should be absolutely stable and without
vibration. Generally, when the post is set into the ground,
the portion below grade should be set in concrete at least
1 meter deep.
4.3
A2306
E-3
cAlibrAtion
To initiate zero calibration of the OPECL from the UD10
Display:
1. Using the magnet to activate the switches on the
UD10 display, navigate to the "Calibration" menu.
Main Menu
Process Vars
Display Status
Device Calibration
Device Status
Cal Gas Type
Display Setup
Zero Cal
Device Setup
Span Cal
Device Cal
Cal Date
Display Test
Device Test
2. Activate "Execute" (Enter/Select) to start calibration.
3. The UD10 will display "Waiting for Zero" on the main
display screen, with a solid red LED on the OPECL
housing illuminated.
4. After the calibration is successfully completed, the
UD10 automatically returns to the normal display with
the green LED illuminated on the OPECL housing.
Calibration
Execute
Abort
95-8618