8.2.3

Power supply fault.

The following table contains a selection of possible errors. You can see how these errors are
displayed and what you have to do to rectify the error.
Error
48 V input voltage is missing
permanently
Input voltage 48 V missing
max. 250 ms or short-term
interruption of the
synchronization signal at the
PSB-C module
Polarity reversal of the 48 V
input voltage
Input SYNC is not connected,
or the synchronization signal is
not generated
Input SYNC it is connected,
the frequency of the
synchronization signal is too
high
Short-circuit on RAIL
Short-circuit at RAIL A and
RAIL B of a plant segment.
Polarity reversal on RAIL
Polarity reversal at RAIL A and
RAIL B of a plant segment.
PSB modules
Operating Instructions, 03/2014, A5E03474166-03
Diagnostics event
A combination of the following diagnostics events is triggered:
Error
Unknown error 000B
The following diagnostics event is triggered:
Error
A combination of the following diagnostics events is triggered:
Process interrupt lost/sampling error
Unknown error 000B
The bridging of two PSB-S modules may result in the
communication failure of several PSB-S modules.
The SYNC LED is inactive
The ERR RAIL LEDs do not provide optical feedback
The "Process interrupt lost/sampling error" diagnostics event is
displayed in STEP 7
The SYNC LED is active
The "Process interrupt lost/sampling error" diagnostics event is
displayed in STEP 7
Reduce the clock frequency for the synchronization signal.
Plant segment controller
The following diagnostic events are triggered:
ERR RAIL LEDs 1 to 3 are active
The presence and validation bit in the PII are set to zero
Carrier controller
The following diagnostic events are triggered:
SYNC LED is inactive
ERR RAIL LED is active
Process interrupt lost/sampling error
The data corresponds to the last data read.
Error on overload and short-circuit on RAIL
While the polarity is reversed on rail RAIL, only the ERR RAIL LEDs
of the PSB-S module at the plant segments where polarity is not
reversed are lit. The ERR RAIL LED of the plant segment at which
polarity is reversed is switched off.