Securing The Cables - Siemens SIMATIC EMS400S PSB-S Operating Instructions Manual

Hide thumbs Also See for SIMATIC EMS400S PSB-S:
Table of Contents

Advertisement

Installing and wiring PSB module

4.6 Securing the cables

Procedure
1. Open the contact cover.
2. Loosen the relevant clamping screw on the terminal block.
3. Insert the conductor into the corresponding terminal.
Observe the terminal labeling on the enclosure. Do not confuse the conductors.
When using flexible conductors:
Ensure that no wire strands protrude from the terminals.
4. Tighten the clamping screws.
Close all contact covers on the PSB module on completion of the wiring.
4.6
Securing the cables
Requirement
● All cables are connected.
Procedure
1. Tie the connected cables to form a harness.
2. Provide a suitable strain relief in the control cabinet to secure the cable harness.
28
NOTICE
Communication failure of PSB-S modules in case of polarity reversal
The polarity reversal of the 48 V connectors of a PSB-S module may result in the
communication failure of several PSB S modules during travel.
Ensure the correct polarity.
Refer to the "EMS400S Plant controller for Electric Monorail Systems" system manual
and the "EMS400S Diagnostics Unit" operating instructions, see Preface (Page 3).
Malfunction or damage in case of polarity reversal on the PSB-C module
The polarity reversal of the 24 V connectors of a PSB-C module may result in equalizing
currents and equalizing voltages at the analog output of the PSB C module. The result
may be malfunctions or damage of the device connected to the analog output.
Ensure the correct polarity.
Additional information is available in the "S7-1200 Automation System" system manual.
Operating Instructions, 03/2014, A5E03474166-03