Siemens SIMATIC EMS400S PSB-S Operating Instructions Manual page 50

Hide thumbs Also See for SIMATIC EMS400S PSB-S:
Table of Contents

Advertisement

Diagnostics options for PSB modules
8.2 Messages and errors
● Group error in the STEP-7 diagnostic buffer
Note
The "Error" event is displayed as incoming and then immediately as outgoing at the
startup of a PSB-S module. This system-related event is triggered during startup and
does not represent an error.
50
Diagnostic entry
Error
Unknown error 000B
Unknown error 000C
Description
Applies to the plant segment controller:
General device error on RAIL 1 to 3
Error in carrier controller. Such events may, for example, include an
interruption of the power supply. It is not necessary to examine the
EMS carrier.
Plant segment controller
Check whether the 48 V input voltage is present. If yes, the
PBS-S module has failed. Return the PSB-S module to Siemens
for repairs.
Carrier controller
Check whether the 24 V input voltage is present. If yes, the
PBS-C module has failed. Return the PSB-C module to Siemens
for repairs.
Applies only to the carrier controller:
Configuration error. The 10-bit range of the analog output is exceeded.
Check the corresponding STEP 7 project.
Operating Instructions, 03/2014, A5E03474166-03
PSB modules