Check code
6607
(A7)
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Continued from the previous page.
Is the correct kind of transmission
line used?
Is it operating in multi refrigerant
system?
When operating in a multi refrigerant system (2 or
more outdoor units), check if any of the indoor unit
stores non-existing address information.
Is the address information correct?
Replace the controller board which the
displayed address/attribute belongs to.
Does it operate normally?
OCH675D
Diagnosis
Yes
Yes
Yes
Yes
No ACK error
Apply the correct kind of transmission line,
No
then perform the procedure 1.
When operating in a single refrigerant
system (single indoor unit), the controller of
No
the displayed address/attribute is defective.
Delete the unnecessary address using
No
a manual setting function on the remote
controller (only for operating in a system
with the Fresh Master/Lossnay is
connected, or in a multi refrigerant system
with group setting is set).
Defective outdoor controller board (repeater
circuit) on the outdoor unit is suspected.
No
Replace the outdoor controller board one
by one, then check for normal operation.
80
Chart 4 of 4
Remedy
Complete.