Mitsubishi Electric PUMY-P200YKM2 Technical & Service Manual page 26

Split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P200YKM2:
Table of Contents

Advertisement

7-4. SYSTEM CONTROL
7-4-1. Example for the System
• Example for wiring control cables, wiring method and address setting, permissible lengths, and the prohibited items are listed
in the standard system with detailed explanation.
A. Example of an M-NET remote controller system (address setting is necessary.)
Example of wiring control cables
1. Standard operation
L
1
OC
(51)
TB3
TB7
M1 M2
S
M1 M2 S
M-NET RC
(101)
• 1 remote controller for each indoor unit
• There is no need for setting the 100 position on the remote
controller.
2. Operation using 2 M-NET remote controllers
OC
(51)
TB3
TB7
M1 M2 S
M1 M2 S
A B
M-NET RC
(101)
(Main)
• Using 2 remote controllers for each indoor unit
3. Group operation
OC
(51)
TB3
TB7
M1 M2 S
M1 M2 S
M-NET RC
• Multiple indoor units operated together by 1 remote control-
ler
Combinations of 1 through 3 above are possible.
OCH675D
L
2
M-IC
M-IC
(01)
(02)
TB5
TB15
TB5
TB15
M1 M2 S
1 2
M1 M2 S
1 2
A B
M-NET RC
A B
(102)
M-IC
M-IC
(01)
(02)
TB5
TB15
TB5
TB15
M1 M2 S
1 2
M1 M2 S
1 2
A B
A B
A B
M-NET RC
M-NET RC
M-NET RC
(151)
(102)
(152)
(Sub)
(Main)
(Sub)
M-IC(Main)
M-IC(Sub)
(01)
(02)
TB5
TB15
TB5
TB15
1 2
M1 M2 S
M1 M2 S
A B
(101)
Wiring Method and Address Setting
a. Use feed wiring to connect terminals M1 and M2 on trans-
mission cable block (TB3) for the outdoor unit (OC) to ter-
minals M1 and M2 on the transmission cable block (TB5)
of each indoor unit (M-IC). Use non-polarized 2-core wire.
b. Connect terminals M1 and M2 on transmission cable termi-
nal block (TB5) for each indoor unit with the terminal block
(TB6) for the M-NET remote controller (M-NET RC).
c. Set the address setting switch (on outdoor unit P.C.B) as
shown below.
Unit
CITY MULTI series
indoor unit (M-IC)
Outdoor unit(OC)
M-NET remote controller
(M-NET RC)
a. Same as above 1.a
b. Same as above 1.b
c. Set address switch (on outdoor unit P.C.B) as shown
below.
Unit
CITY MULTI series
indoor unit (M-IC)
Outdoor unit (OC)
Main M-NET
remote controller
(M-NET RC)
Sub M-NET
remote controller
(M-NET RC)
a. Same as above 1.a
b. Connect terminals M1 and M2 on transmission cable termi-
nal block (TB5) of the M-IC main unit with the most recent
address within the same indoor unit (M-IC) group to terminal
block (TB6) on the remote controller.
c. Set the address setting switch (on outdoor unit P.C.B) as
shown below.
1 2
Unit
M-IC (Main)
M-IC (Sub)
Outdoor unit
Main Remote
Controller
Sub Remote
Controller
d. Use the indoor unit (M-IC) within the group with the
most functions as the M-IC (Main) unit.
26
Range
Setting Method
001 to 050
Use the smallest address of all the
051 to 100
indoor unit plus 50.
101 to 150 Indoor unit address plus 100
Range
Setting Method
001 to 050
Use the smallest address of all
051 to 100
the indoor units plus 50.
101 to 150 Indoor unit address plus 100
151 to 200 Indoor unit address plus 150
Range
Setting Method
Use the smallest address within the
001 to 050
same group of indoor units.
Use an address, other than that of
the M-IC (Main) from among the units
within the same group of indoor
001 to 050
units. This must be in sequence with
the M-IC (Main).
Use the smallest address of all the
051 to 100
indoor units plus 50.
Set at an M-IC (Main) address within
101 to 150
the same group plus 100.
Set at an M-IC (Main) address within
151 to 200
the same group plus 150.