Cross section area of Wire for Main Power and ON/OFF capacities
9-2-1.
PUMY-P200YKM2
PUMY-P200YKM2R1
<Outdoor unit> <When power is supplied to outdoor unit and branch box separately>
Power Supply
Model
3N~380-400-415 V
Outdoor
P200
unit
<Outdoor unit> <When power is supplied to branch box from the outdoor unit>
Power Supply
Model
3N~380-400-415 V
Outdoor
P200
unit
A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*
1
<Indoor units> <When power is supplied to indoor unit and outdoor unit separately>
Total operating current
of the indoor unit
F0 = 16A or less *
3
F0 = 25A or less *
3
F0 = 32A or less *
3
Apply to IEC61000-3-3 about max. permissive system impedance.
The Ground-fault interrupter should support inverter circuit.
*2
The Ground-fault interrupter should combine using of local switch or wiring breaker.
Please take the larger of F1 or F2 as the value for F0.
*3
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type1)/C} + {V1 × (Quantity of Type2)/C} + {V1 × (Quantity of Type3)/C} + · · · + {V1 × (Quantity of Type16)/C}
Connect to Branch box (PAC-MK∙BC)
Indoor unit
SEZ-KD∙VAQ(L), SEZ-M∙DA(L), PCA-RP∙KAQ, PCA-M∙KA,
Type 1
SLZ-KF∙VA, SLZ-M∙FA, PLA-RP∙BA, PLA-RP∙EA, PLA-M∙EA
PEAD-RP∙JAQ(L), PEAD-M∙JA(L)
Type 2
MLZ-KA∙VA, MLZ-KP∙VF
Type 3
Type 4
MSZ-FH∙VE, MSZ-GF∙VE, MSZ-SF∙VE, MSZ-EF∙VE, MSZ-SF∙VA, MSZ-EF∙VG
MFZ-KJ∙VE2, MSZ-LN∙VG, MSZ-AP∙VG, MSZ-AP∙VF
Type 5
Branch box (PAC-MK∙BC)
Type 6
Connect to Connection kit (PAC-LV11M)
Indoor unit
MSZ-EF∙VE, MSZ-SF∙VA, MSZ-SF∙VE, MSZ-FH∙VE, MSZ-EF∙VG
Type 7
MFZ-KJ∙VE2, MSZ-LN∙VG, MSZ-AP∙VG, MSZ-AP∙VF
Type 8
Connection kit (PAC-LV11M)
Type 9
Indoor unit
PEFY-P∙VMA(L)-E, PEFY-P∙VMA3-E
Type 10
Type 11
PMFY-P∙VBM-E, PLFY-P∙VBM-E, PEFY-P∙VMS1-E, PCFY-P∙VKM-E,
PKFY-P∙VHM-E, PKFY-P∙VKM-E, PLFY-P∙VEM-E, PLFY-EP∙VEM-E
Type 12
PLFY-P∙VFM-E, PFFY-VKM-E2, PFFY-VLRMM-E, PKFY-VLM-E
PEFY-P∙VMA(L)-E3
Type 13
Type 14
PEFY-P∙VMH(S)-E
PKFY-P∙VBM-E
Type 15
PLFY-P∙VLMD-E, PEFY-P∙VMR-E-L/R, PEFY-P∙VMH-E-F, PDFY-P∙VM-E,
Type 16
PFFY-P∙VLEM-E, GUF-∙RD(H)4, PEFY-VMH-E, PFFY-VLRM-E
C : Multiple of tripping current at tripping time 0.01s
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
*Condition PLFY-P∙VBM-E × 4 + PEFY-VMA-E × 1, C = 8 (refer to right sample chart)
F2 = 19.8 × 4/8 + 38 × 1/8
= 14.65 → 16 A breaker (Tripping current = 8 × 16 A at 0.01 s)
*4 Current sensitivity is calculated using the following formula.
G1 = V2 × (Quantity of Type 1) + V2 × (Quantity of Type 2) + V2 × (Quantity of Type 3) + ··· + V2 × (Quantity of Type 16)+ V3 × (Wire length [km])
Notes:
1. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
2. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10%.
3. Specific wiring requirements should adhere to the wiring regulations of the region.
4. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 60245 IEC57). For
example, use wiring such as YZW.
5. install an earth line longer than power cables.
OCH675D
PUMY-P200YKM2-BS
PUMY-P200YKM2R1-BS
Minimum Wire Cross-section-
al area (mm
Main
Cable
2.5
50 Hz
Minimum Wire Cross-section-
al area (mm
Main
Cable
4.0
50 Hz
Minimum wire thickness
(mm
2
)
Main
Branch
Ground
Cable
1.5
1.5
1.5
2.5
2.5
2.5
4.0
4.0
4.0
Breaker
2
)
for Wiring *
1
Ground
2.5
25 A
Breaker
)
2
for Wiring *
1
Ground
4.0
32 A
Ground-fault interrupter *
20 A current sensitivity *
30 A current sensitivity *
40 A current sensitivity *
V1
19.8
26.9
9.9
6.8
7.4
5.1
V1
6.8
7.4
3.5
V1
38.0
19.8
18.6
13.8
3.5
0.0
117
Breaker for Current Leakage
25 A 30 mA 0.1 s or less
Breaker for Current Leakage
32 A 30 mA 0.1 s or less
Local switch (A)
Breaker for
2
wiring (NFB)
Capacity
Fuse
4
16
16
4
25
25
4
32
32
V2
Sample chart
6000
2.4
600
60
3.0
10
V2
1
2.4
0.1
V2
1.6
0.01
1
2
3
2.4
Rated Tripping current (x)
3.0
4.8
2.4
G1
Current sensitivity
30 or less
30 mA 0.1 sec or less
0.0
100 or less
100 mA 0.1 sec or less
Wire thickness
1.5 mm²
2.5 mm²
4.0 mm²
20
30
40
4
6
8
10
20
C
V3
48
56
66