D. Example of a group operation with 2 or more outdoor units and an MA remote controller.
(Address settings are necessary.)
L
2
L
6
A : Group
B : Group
C : Group
D : Shielded Wire
E : Sub Remote Controller
( ): Address example
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (M-IC), as
well for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3)
of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable block of the indoor unit
(M-IC).
c. Connect terminals 1 and 2 on the terminal block for MA remote controller line (TB15) on the indoor unit (IC) to the
terminal block on the MA remote controller (MA-RC). (Nonpolarized two-wire)
d. Connect together terminals M1, M2 and terminal S on the terminal block for centralized control (TB7) for the outdoor unit (OC).
e. DO NOT change the jumper connector CN41 on MULTI controller circuit board.
f. The earth processing of S terminal for the centralized control terminal block (TB7) is unnecessary. Connect the termi-
nal S on the power supply unit with the earth.
g. Set the address setting switch as follows.
Unit
IC (Main)
IC (Sub)
OC
Main M-NET Remote Controller
Sub M-NET Remote Controller
MA Remote Controller
OCH675D
OC
(51)
TB7
TB3
M1 M2 S M1 M2 S
D
L
3
OC
(53)
NO
TB3
TB7
M1 M2 S
M1 M2 S
Power Supply
Unit
M1 M2 S
D
System
controller
M1 M2 S
Range
Use the smallest address within the same group of indoor units.
01 to 50
Use an address, other than the IC (Main) in the same group of indoor units.
01 to 50
This must be in sequence with the IC (Main).
Use the smallest address of all the indoor units plus 50.
51 to 100
The address automatically becomes "100" if it is set as "01–50".
Set at an IC (Main) address within the same group plus 100.
101 to 150
Set at an IC (Main) address within the same group plus 150.
151 to 200
Address setting is not necessary. (Main/ sub setting is necessary.)
L
1
A
M-IC
M-IC
m
2
(01)
(02)
TB5
TB5
TB15
TB15
M1 M2 S
M1 M2 S
1 2
1 2
A B
MA-RC
L
4
M-IC
M-IC
(04)
(03)
TB5
TB15
TB5
TB15
M1 M2 S
M1 M2 S
1 2
1 2
A B
MA-RC
B
Setting Method
32
C
M-IC
M-IC
m
2
(05)
(06)
TB5
TB5
TB15
TB15
M1 M2 S
M1 M2 S
1 2
1 2
A B
A B
MA-RC
MA-RC
E
M-IC
(07)
TB5
TB15
M1 M2 S
1 2