Mitsubishi Electric PUMY-P200YKM2 Technical & Service Manual page 8

Split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P200YKM2:
Table of Contents

Advertisement

2-4. SYSTEM SPECIFICATIONS
(1) Outdoor Unit
Service Ref.
Cooling (kW)
Capacity
Heating (kW)
Compressor (kW)
Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling
Indoor : D.B. 27°C/W.B. 19.0°C
Outdoor: D.B. 35°C
Heating
Indoor : D.B. 20°C
Outdoor: D.B. 7°C/W.B. 6°C
(2) Method for identifying MULTI-S model
Outdoor unit <When using model 200 >
PU M Y ─ P 200 Y K M 2 ─ BS
Outdoor unit
Refrigerant
MULTI-S
Frequency
conversion
controller
Indicates equivalent
to Cooling capacity(kcal/ h)
(3) Operating temperature range
Indoor-side intake air temperature
Outdoor-side intake air temperature
Notes:
D.B.: Dry Bulb Temperature
W.B.: Wet Bulb Temperature
*
10 to 52°C D.B.: When connecting PKFY-P15/20/25VBM, PKFY-P10/15/20/25/32VLM, PFFY-P20/25/32VKM, PFFY-P20/25/32VLE(R)M,
PEFY-P40/63VMA3-E; and M series, S series, and P series type indoor unit.
■ When connecting fresh air type indoor unit
• PEFY-P·VHM-E-F
Indoor-side and Outdoor-side intake air temperature
*Thermo-OFF (FAN-mode) automatically starts if the outdoor temperature is lower than 21ºC D.B.
**Thermo-OFF (FAN-mode) automatically starts if the outdoor temperature is higher than 20ºC D.B.
OCH675D
PUMY-P200YKM2(R1)
PUMY-P200YKM2(R1)-BS
R410A
M-NET
control
Outdoor unit
model type
Power supply
Y: 3-phase
380-400-415 V, 50/60 Hz
Cooling
W.B. 15 to 24°C
D.B. −5 to 52°C
(Only P200)
.
22.4
25.0
5.3
Salt proof
type
Sub-
number
Heating
D.B. 15 to 27°C
W.B. −20 to 15°C
*
Cooling
D.B. 21 to 43ºC*
D.B. −10 to 20ºC**
W.B. 15.5 to 35ºC
8
Heating