Wiring - Mitsubishi Electric VAR-6A User Manual

Automatic power factor controller
Table of Contents

Advertisement

Installation 3. Wiring
1 Solderless Terminal
Use solderless terminal that comply with the size of the electric line.
Connecting Completion Output terminal
Disconnecting Completion Output terminal
Screw Specification
M4 screw
Solderless Terminal
For M4 screw of outer diameter below 8.5
Tighting Torque
0.98 N・m to 1.47 N・m
Outer diameter
2 Terminal Cover
Insert the terminal cover for power
supply into the terminal stand as
shown in the right figure.
Since the terminal cover for input and
output has structure to open
3 Wire connections
Tighten a terminal screw
on the terminal stand.
Do not connect three or more electric wires to one terminal.
CAUTION
It can generate heat and cause a fire.
4 Checking
Check that there is no mistake in wire connections after completing wire connetion.
5 Terminal cover attachment
,
After checking
close the terminal cover till it makes clicking sound.
Connection Disable Input terminal
Disconnection Disable Input terminal
Forced Disconnection Signal terminal
Current Input terminal
Voltage Input terminal
Auxiliary Power terminal
,
close it.
Terminal Cover
Terminal Screw
Control Signal Output terminal
M3.5 screw
For M3.5 screw of outer diameter below 7.1
0.61 N・m to 0.82 N・m
44