Hisense AVWT-76FKFSHA Technical Handbook page 564

Vrf air-conditioner (heat recovery)
Hide thumbs Also See for AVWT-76FKFSHA:
Table of Contents

Advertisement

Setting for Transmitting
It is required to set the outdoor unit Nos., refrigeration cycle Nos. and end terminal resistance for this Hi-
NET system.
Setting of Outdoor Unit No. In case of the combination of base unit, set DSW6 as shown below.
Base Unit
Outdoor Unit A
(Before Shipment)
(No.0)
ON
ON
OFF
OFF
1 2 3 4
1 2 3 4
Setting of Refrigeration Cycle No.
In the same refrigeration cycle, set the refrigeration cycle No. for the outdoor units as shown below.
NOTE: In the same refrigeration cycle, set the same refrigeration cycle No. for the outdoor unit and the
indoor unit.
10 digit
ON
OFF
1 2 3 4 5 6
Outdoor Unit
DSW1
Ex: In Case of Setting Refrigeration Cycle No. 25
ON
OFF
5 6
1 2 3 4
Turn ON No. 1 and No. 3 pins
Turn ON No. 2 pin.
(The settings in binary system shall be
only valid for 0~9 and it will alarm once
exceeding.)
DSW1 and DSW8 setting before shipment is 0.
Maximum in setting refrigeration cycle No. is 63.
Setting of Terminal Resistance
Before shipment, No.1 pin of DSW10 is set at the "ON"side. In the
case that the outdoor units quantity in the same Hi-NET is 2 or more,
set No. 1 pin of DSW10 at the "OFF" side from the 2nd refrigerant
group outdoor unit. If only one outdoor unit is used, no setting is
required.
Outdoor Unit
DSW10
1 2
Communication cable
(Hi-NET)
Indoor
Unit
Combination of Base Unit
Outdoor Unit B
(No.2)
(Main)
ON
OFF
1 2 3 4
Setting Switch
1 digit
ON
OFF
1 2 3 4
DSW8
OFF
1 2 3 4
Set Position 1 on DSW10 to
OFF to cancel setting of
terminal resistance.
Outdoor Unit
DSW10
DSW10
Outdoor 1
2
2
Outdo or 1
Unit B
Unit A
(Main)
(Sub)
Communication cable
(Hi-NET)
Indoor
Unit
Outdoor Unit C
Outdoor Unit D
(No.3)
(No.4)
ON
ON
OFF
OFF
1 2 3 4
1 2
0
1
2
3
4
DSW10
ON
OFF
1 2
Outdoor Unit
DSW10
DSW10
Outdoor 1
Outdoor 1 2
2
Unit C
Unit A
(Sub)
(Main)
Communication cable
Indoor
Unit
557
3 4
0~9 Binary System Dip Setting Method for DSW8
ON
OFF
5
1 2 3 4
ON
OFF
6
1 2 3 4
ON
OFF
7
1 2 3 4
ON
OFF
8
1 2 3 4
ON
OFF
9
1 2 3 4
Setting of End Terminal Resistance
DSW10
Cancellation
Before Shipment
ON
OFF
1
1
2
Set Position 1 on DSW10 to
OFF to cancel setting of
terminal resistance.
Outdoor Unit
DSW10
Outdo
or 1 2
Unit B
(Sub)
(Hi-NET)
Indoor
Unit
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
2
DSW10
ON
OFF
1 2
DSW10
1 2