3) Walls in 4 Directions
● Single Installation
to
Multiple / Serial Installation
Installation in the Same Direction
Min. 200
No limit to
side wall height
Min. 800
Open
Min. 200 Min. 200
Top View
Rear to Rear Installation 1
Min.200
Side Space
No limit to
side wall height
Min. 800 Open
Min. 200
NOTE:
1. Keep the upper side open to prevent mutual interference of inlet and outlet air of each outdoor unit.
2. The dimensions in figure are sufficient spaces around outdoor units for operation and maintenance at typical installing
conditions as follows.
[ Operation Mode: Cooling Operation, Outside Temp.: 35oC ] In case that the outdoor unit ambient temperature is higher and
also the short circuit is likely to occur compared to the installation condition, find an appropriate dimension by calculating air
flow current.
3.
For the multiple installation, 1 group allows 6 outdoor units (max.).
The space of 1m between each group is required.
4. Partly open a wall if the unit is surrounded by walls in four directions.
to
Min. 300+h1/2
Min. 200
Front
Min. 900
Front
Front
Min. 500+h2/2
Min. 500+h2/2
Front
Min. 200
Min. 1600
No limit to
side wall height
Min. 800 Open
Front
Min. 200 Min. 200
Min. 500+h2/2
Top View
1 Group (Max. 6 Outdoor Units)
Min. 800
Open
Min. 200
No limit to
side wall height
Min. 800 Open
Min. 1m
538
Rear to Rear Installation 2
Front
Min. 900
Rear Space
Min. 200
Min. 500+h2/2
Min. 400 Min. 400
Min. 400
Top View
Min. 500+h2/2
Min. 200
No limit to side
wall height
Min. 800 Open