Hisense AVWT-76FKFSHA Technical Handbook page 541

Vrf air-conditioner (heat recovery)
Hide thumbs Also See for AVWT-76FKFSHA:
Table of Contents

Advertisement

○ : Interchangeable current R22
X : Prohibited
Interchangeability
with
Measuring Instrument
and Tool
R407C
Pipe Cutter
Chamfering
Reamer
Flaring Tool
Allowance
Adjustment
Gauge
Pipe Bender
Refrige-
Expanding
rant
Tool
Pipe
Torque
Wrench
Brazing Tool
Nitrogen Gas
Lubrication Oil
(for Flare
Surface)
Refrigerant
Cylinder
Vacuum Pump
Adapter for
Vacuum
Interchangeability
PumpReverse
with R410A
flow prevention
Refrige-
rant
Control Valve
Charge
Charging
Vacuum
Hose
Drying
Charging
Cylinder
Weight Scale
Refrigerant
Gas Leakage
Interchangeability
Detector
with R410A
Interchangeable with R407C
R22
R410A
R410A requires high pressure resistance piping and
*
○■
larger flaring process. In case of material 1/2H, flaring is
not applicable. (The flaring tools for R410A are
applicable to R407C)
In case of material 1/2H, bending is not applicable. Use elbow
*
for bend and braze.
In case of material 1/2H, expanding of tube is not applicable.
*
Use socket for connecting tube.
For Φ12.7, Φ15.88 of R410A, spanner size is up 2mm
*
For Φ6.35, Φ9.53, Φ19.05, spanner size is the same.
*
Perform brazing work(adjustable flame, heating
*
method, feeding filler) properly
Strict Control against Contamination (Purge nitrogen during
*
brazing.)
Use a synthetic oil which is equivalent to the oil used in the
*
refrigeration cycle.
Synthetic oil absorbs moisture quickly.
*
Check the cylinder for the corresponding refrigerant.
*
★ It is a must to charge liquid zeotropic refrigerant.
★The current ones are applicable. However, it is required to
※■
mount a vacuum pump adapter which can prevent from reverse
flow when a vacuum pump stops.
The higher pressure compared with R22 accounts for
*
non-interchangeability. Connection diameter is different:
R410A: UNFl/2, R407C: UNF7/16
★Do not use old ones to the different refrigerant. If used, mineral
oil will flow into the cycle and cause sludges, resulting in
clogging or compressor failure.
Use the weight scale
*
×
The current gas leakage detector (R22) is not applicable due
※■
*
to different detecting method.
■: only for Refrigerant R410A (No Interchangeability with R22)
● : only for Refrigerant R407C (No Interchangeability with R22)
Reason of Non-Interchangeability
and Attention (★: Strictly Required)
——
——
534
Use
Cutting Pipe
Removing Burrs
Flaring for Tubes
Dimensional Control for Ex-
truded Portion of Tube after
Flaring
Bending
Expanding Tubes
Connection of Flare Nut
Brazing for Tubes
Prevention from Oxidation
during Brazing Air-tight test
Applying Oil to the Flared
Surface
Refrigerant Charging
Vacuum Pumping
Vacuum Pumping, Vacuum
Holding, Refrigerant Charg-
ing and Check of Pressures
Refrigerant Charging
Measuring Instrument for
Refrigerant Charging Gas
Leakage Check