PDU8000 Modular Precision PDC V2.0
User Manual
Connection Method
● Keep away from cabinets when preparing cables to prevent cable scraps from
● After installing cables, clean the cabinet top, bottom, copper bar wiring
● Prepare terminals onsite. The length of the copper wire should be the same as
Step 1 Route a cable into the cabinet and bind it to a nearby beam.
Step 2 Pull the cable to the copper bar to which the cable is to be connected, determine
the cable length, and mark the cable at the position where the cable is to be cut.
Step 3 Pull the marked cable out of the cabinet, cut the cable from the marked position,
strip the cable, and crimp a terminal.
Figure 5-29 Preparing a cable terminal outside the cabinet
Step 4 Connect the cable with a crimped terminal to the corresponding copper bar.
Step 5 Clean foreign matter inside the cabinet.
----End
Issue 04 (2021-04-13)
NO TE
● This document uses the dual-input top cable routing and single-input bottom cable
routing as examples. Cable connections for other scenarios are similar.
● Remove the rodent-proof mesh at the top or bottom based on the cable routing
scenario.
CA UTION
entering the cabinets. Cable scraps may cause ignition during power-on and
result in personal injury and device damage.
positions, and other positions. Ensure that there is no dust or scraps inside and
around cabinets.
that of the part of the terminal that covers the conductor.
NO TE
Choose an appropriate cabling route based on the actual situation. The figure is for
reference only.
Copyright © Huawei Technologies Co., Ltd.