PDU8000 Modular Precision PDC V2.0
User Manual
Figure 7-35 Threshold (1)
Figure 7-36 Threshold (2)
The value ranges from 0 to 60.
Specifies the upper alarm threshold in relative to the rated voltage. The value
ranges from 105 to 125.
Specifies the duration for confirming an overvoltage alarm. The value ranges from
1 to 10.
Issue 04 (2021-04-13)
Open phase voltage (V)
System overvoltage (%)
Overvoltage ack.time (s)
Copyright © Huawei Technologies Co., Ltd.
7 MDU Commissioning Guide
93