Huawei PDU8000 User Manual page 22

Modular precision pdc
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Precision PDC V2.0
User Manual
Item
Enclosure
protection level
Output circuit
breakers
Surge protection
Cabling
Environmental
friendliness
Overvoltage level
Operating
temperature
Relative humidity
Altitude
Table 3-3 Safety and EMC
Item
Safety
EMC
Issue 04 (2021-04-13)
Specifications
IP20
Single- or three-phase 16 A/20 A/32 A/40 A/63 A;
maximum: 144 single-phase routes or 48 three-phase
routes
Class C SPD in standard configuration
● 400 A/250 A/160 A input scenario: Cables can be routed
in and out from the top or bottom.
● 630 A input scenario: Cables can be routed in from the
top and out from the top or bottom.
RoHS, REACH
II
–5°C to +40°C
5%–95%, non-condensing
≤ 2000 m (If the altitude exceeds 2000 m, the device is
derated according to GB/T3859.2-93.)
Specifications
CCC, CE, TL
Conducted emission (CE)
Radiated emission (RE)
Voltage fluctuation and
flicker
Harmonic current
Conducted susceptibility
(CS)
Radiated susceptibility
(RS)
Electrostatic discharge
(ESD)
Copyright © Huawei Technologies Co., Ltd.
N/A
EN55022 CLASS A
EN55022 CLASS A
EN61000-3-3
EN61000-3-11
EN61000-3-2
EN61000-3-12
IEC61000-4-6
IEC61000-4-3
IEC61000-4-2