PDU8000 Modular Precision PDC V2.0
User Manual
Alarm
Name
Br. circuit
breaker off
Branch
abnormal
Branch
overload
Max. br.
cur. exceed
Min. br. cur.
exceed
Issue 04 (2021-04-13)
Alarm
Impact
Severity
Critical
A branch
switch has
changed from
ON to OFF.
Warning
A branch
switch is on,
but no current
is detected.
Critical
The current of
a branch
exceeds 1 time
of the rated
current
(multiple: 1–
1.2;
confirmation
time: 1–10s).
Major
The current of
a branch
exceeds 0.8
time of the
rated current
(multiple: 0.8–
1).
Warning
The current of
a branch
exceeds 0.6
time of the
rated current
(multiple: 0.6–
0.8;
confirmation
time: 1–10s).
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance Guide
Possible
Solutions
Cause
A branch
If you do not to
switch is off.
display a Br. circuit
breaker off, you set
Br. circuit breaker
off to Custom, and
set the branch to
Disable.
MDU path: System
Info. > Setting >
System Param.
No loading
If you do not to
display a Branch
abnormal, you set
Branch abnormal
to Custom, and set
the branch to
Disable.
MDU path: System
Info. > Setting >
System Param.
The branch
Check the load
is
power of the
overloaded.
branch.
The branch
Check the load
is
power of the
overloaded.
branch.
N/A
N/A
119