LG ARND DCR4 Series Installation Manual page 55

Split compact dedicated outdoor air system (doas)
Hide thumbs Also See for ARND DCR4 Series:
Table of Contents

Advertisement

Table 27: BACnet / Modbus Points List for DOAS Units Table, continued.
Variable
I073_SAFanOperationRate
I074_EAFanOperationRate
I075_ERWOperationRate
I076_MainCoilOperationRate
I077_ReheatCoilOperationRate
I078_PreheatCoilOperationRate
I079_RecoveryCoilOperationRate
I080_TargetHighPressure
I081_TargetLowPressure
I084_ReheatCoilEEVPulse
I086_SAFanFlowVolume
I087_EAFanFlowVolume
I9004_ODU1_HighPressureTrace
I9005_ODU1_LowPressureTrace
I9012_ODU1_Inv1Trace
I9014_ODU1_Inv2Trace
I9015_ODU1_Fan1Trace
I9016_ODU1_Fan2Trace
I9023_ODU1_AirTemp
I9024_ODU1_SuctionTemp
I9025_ODU1_CondeseTemp
I9026_ODU1_EvaporateTemp
I9036_ODU1_Inv1IPMTemp
I9037_ODU1_Inv2IPMTemp
I9038_ODU1_Inv1InputCT
I9039_ODU1_Inv2InputCT
I9040_ODU1_Inv1InputVT
I9041_ODU1_Inv2InputVT
I9042_ODU1_Inv1PhaseCT
I9043_ODU1_Inv2PhaseCT
Description
Supply Fan Motor Speed (%)
Exhaust Fan Motor Speed (%)
Energy Recovery Wheel Motor
Speed (%) by Cycle Period
Target Pressure Adjustment
Value (%) by Cycle Period
Reheat Coil EEV Adjustment
Value (%) by Cycle Period
Electric Heater
Recovery Coil EEV Adjustment
Value (%) by Cycle Period
Target High Pressure of
Outdoor Unit
Target Low Pressure of
Outdoor Unit
Reheat Coil EEV Pulse Value
Supply Air Flow Rate
Exhaust Air Flow Rate (if
Differential Pressure Sensor is
equipped)
ODU Main High Pressure
ODU Main Low Pressure
ODU Main Inverter #1
Compressor Hz
ODU Main Inverter #2
Compressor Hz
ODU Main Fan #1 RPM
ODU Main Fan #1 RPM
ODU Main Ambient
Temperature
ODU Main Suction Pipe
Refrigerant Temperature
ODU Main Condenser
Refrigerant Temperature
ODU Master Evaporator
Refrigerant Temperature
ODU Main Inverter #1
Heat-Sink Temperature
ODU Main Inverter #2
Heat-Sink Temperature
ODU Main Inverter #1 Input
Current (CT)
ODU Main Inverter #2 Input
Current (CT)
ODU Main Inverter #1 Input
Voltage
ODU Main Inverter #2 Input
Voltage
ODU Main Inverter #1 Phase
Current
ODU Main Inverter #2 Phase
Current
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
BACnet
Active
Inactive
Text
Text
Access
ReadCOV_NoWrite
ReadCOV_NoWrite
ReadCOV_NoWrite
ReadCOV_NoWrite
ReadCOV_NoWrite
Read_NoWrite
ReadCOV_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
ReadCOV_NoWrite
ReadCOV_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Read_NoWrite
Modbus
COV
Register
x 0.1
Index
Size
Incre.
Type
1
30074
Input
2
1
30075
Input
2
1
30076
Input
2
1
30077
Input
2
1
30078
Input
2
30079
Input
2
1
30080
Input
2
30081
Input
2
30082
Input
2
30085
Input
2
2
30087
Input
2
2
30088
Input
2
39005
Input
2
39006
Input
2
39013
Input
2
39015
Input
2
39016
Input
2
39017
Input
2
39024
Input
2
39025
Input
2
39026
Input
2
39027
Input
2
39037
Input
2
39038
Input
2
39039
Input
2
39040
Input
2
39041
Input
2
39042
Input
2
39043
Input
2
39044
Input
2
Req.
55

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Arnd203dcr4Arnd153dcr4

Table of Contents