LG ARND DCR4 Series Installation Manual page 34

Split compact dedicated outdoor air system (doas)
Hide thumbs Also See for ARND DCR4 Series:
Table of Contents

Advertisement

ELECTRICAL SYSTEM
Terminal Connections for Electrical Components
NTC Module
Figure 22: NTC Module.
Table 17: NTC Module Component Details.
Drawing
Label
Reference
2
CH1
CH1 port of Other module for communication
RI1
Space / Return Duct Temperature (Field Option)
RI2
RI3
RI4
3
RI5
RI6
RI7
RI8
34
Unit Connection
Unassigned
Outdoor Air Temperature
Leaving Air Temperature (Main Coil) #1
Leaving Air Temperature (Main Coil) #2
Exhaust Air Temperature
Supply Air Temperature
Outdoor Air Temperature After Wheel
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Position
Sensor Type
Indicates
RS-485
NTC 10k
NTC 10k
NTC 10k
NTC 10k
NTC 10k
NTC 10k
NTC 10k
NTC 10k
Range
-130-210°F
-130-210°F
-130-210°F
-130-210°F
-130-210°F
-130-210°F
-130-210°F
-130-210°F