Conditions

Obey the installation conditions specified in this guide to take full advantage of the finless
design of this drive.

Installation Environment

The installation environment is important for the lifespan of the product and to make sure that
the drive performance is correct. Make sure that the installation environment agrees with the
specifications shown in
Environment
Indoors
Area of Use
Overvoltage Category III (IEC60664)
Power Supply
-10 °C to +35 °C (14 °F to 95 °F)
• Drive reliability is better in environments where the temperature does not increase or decrease
quickly.
Ambient
• When you install the drive in an enclosure, use a cooling fan or air conditioner to keep the internal
Temperature
air temperature in the permitted range.
Setting
• Do not let the drive freeze.
• You can use finless-type drives at a maximum of +50 °C (122 °F) when you derate the output
current.
95%RH or less
Humidity
Do not let condensation form on the drive.
Storage
-20 °C to +70 °C (-4 °F to +158 °F) (short-term temperature during transportation)
Temperature
Pollution degree 2 or less (IEC 60664-1)
Install the drive in an area without:
• Oil mist, corrosive or flammable gas, or dust
• Metal powder, oil, water, or other unwanted materials
• Radioactive or flammable materials.
Surrounding Area
• Harmful gas or fluids
• Salt
• Direct sunlight
Keep wood and other flammable materials away from the drive.
1000 m (3281 ft) Maximum
Altitude
• 10 Hz to 20 Hz: 1 G (9.8 m/s
Vibration
• 20 Hz to 55 Hz: 0.6 G (5.9 m/s
Installation
Install the drive vertically for sufficient airflow to cool the drive.
Orientation
YASKAWA TOEP C710617 0SA YASKAWA AC Drive GA500 Installation Manual
Table
5.1.
Table 5.1 Installation Environment
*1
Note:
Derate the output current by 1% for each 100 m (328 ft) to install the drive in altitudes between
1000 m to 4000 m (3281 ft to 13123 ft).
It is not necessary to derate the rated voltage in these conditions:
• When you install the drive at 2000 m (6562 ft) or lower
• When you install the drive between 2000 m to 4000 m (6562 ft to 13123 ft) and ground the
neutral point on the power supply.
Contact Yaskawa or your nearest sales representative if you will not ground the neutral point.