8-4. Address setup

This product requires address setup before operation.
Follow this procedure for address setup.

8-4-1. Precautions

(1) Address setup is not performed simply by turning on the power supply.
(2) For indoor units, address setup can be done either by manual address setup or by automatic address setup:
Automatic address setup: Setup from SW15 on the interface P.C. board of the outdoor unit
Manual address setup: Setup from the wired remote controller. (For details, refer to "8-4-3. Address setup
procedure.")
(3) Automatic setup usually takes about 5 minutes per line. In some cases, however, it may take up to 10 minutes.
(4) It is unnecessary to operate the air conditioner to achieve address setup.

8-4-2. Address setup and check procedure

P
o r
c
e
d
u
e r
I
e t
m
1
Indoor unit power-on
Outdoor unit power-on
2
7-segment display
3
check
Address setup start
4
Display check after
5
setup
System information
check after setup
6
Interface P.C. board
SW06
SW07
SW09
SW10
SW11
SW12 SW13
SW14
SW16
SW17
SW30
Turn on the power of the indoor unit for the refrigerant line for which the address is to be set up.
Turn on the power of the outdoor unit for the refrigerant line for which the address is to be set
up.
Check that "L08" is displayed on the 7-segment display [B] on the interface P.C. board of the
outdoor unit in the system where the address is to be set up.
Confirm the items in "8-4-3. Address setup procedure," and then set up the address according
to the operation procedure.
(Be careful to note that the setup operation may differ in group control and central control
systems.)
Note:
The address cannot be set up if switches are not operated.
• After address setup, "U1" " " is displayed on the 7-segment display.
• If an error code is displayed on the 7-segment display [B], remove the cause of the problem
referring to "9 Troubleshooting."
Using the 7-segment display function, check the system information of the scheduled system.
(This check is executed on the interface P.C. board of the outdoor unit.)
System capacity
Total capacity of indoor
units
After the above checks, return rotary switches SW01, SW02, and SW03 to 1/1/1.
SW04
SW05
SW15
Push switch
D600 D601 D602 D603 D604
SW01
SW02
SW03
7-segment
display [A]
45
68
O
p
r e
t a
o i
n
a
n
d
c
h
e
c
k
c
o
n
e t
n
s t
Rotary switch setup
7-segment display
SW01
SW02
SW03
[A]
[Number of
1
2
3
horsepower]
1
3
3
[l. –]
Push switch
SW04
SW05
SW15
7-segment
display [B]
D600 D601 D602 D603 D604
SW01
SW02
SW03
Rotary switches
[B]
[H P]
[–. – –]