Manual Adjustment Function Of Outside Temperature (To) Sensor - Toshiba MCY-MHP0305HT-C Service Manual

Air-conditioner (multi type)
Table of Contents

Advertisement

8-7-9. Manual adjustment function of outside temperature (TO)
sensor
This function is provided to fix TO sensor value manually by the switch operation on the interface P.C. board in the
outdoor unit. When the unit stops abnormally due to TO sensor failure, etc, an emergent operation is available by
setting up the value manually to position near the current outside temperature.
[Operation]
(1) Set the rotary switches on the interface P.C. board to numbers as follows:
SW01 / SW02 / SW03 to [2/1/15]
7-segment display: [ t o ]
(2) Keep pressing the push-switch SW04 on the interface P.C. board for 2 second or more. The mode changes to
the TO sensor value fix manual mode.
(3) As shown in the following table, TO sensor value can be fixed by setting the rotary switch SW02 on the interface
P.C. board.
[Clear]
Return SW01 / SW02 / SW03 on the interface P.C. board in the outdoor unit to [1/1/1].
SW02 7-segment display [B]
1
[ 10. ]
2
[ 15. ]
3
[ 20. ]
4
[ 25. ]
5
[ 30. ]
6
[ 35. ]
7
[ 40. ]
8
[ 43. ]
9
[ 45. ]
10
[ –15. ]
11
[ –10. ]
12
[ – 5. ]
13
[
0. ]
14
[
2. ]
15
[
5. ]
16
[
7. ]
NOTE)
If operated with TO sensor fixed by this function, the system control operation of the air conditioner may
not be based on the specification of the product. Therefore an emergent operation should be restricted
to a day or so.
TO sensor value
10
°C
15
°C
20
°C
25
°C
30
°C
35
°C
40
°C
43
°C
45
°C
-15
°C
-10
°C
-5
°C
0
°C
2
°C
5
°C
7
°C
82
105

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents