Toshiba MCY-MHP0305HT-C Service Manual page 97

Air-conditioner (multi type)
Table of Contents

Advertisement

Check code
Location
Outdoor 7-segment display
Main
remote
detection
Check
Sub-code
controller
code
Remote
controller
E09
Indoor
unit
E10
I/F
E12
E12
I/F
E15
E15
00:
I/F
Overloading
01-:
No. of units
connected
E16
E16
Indoor
unit
E18
01:
I/F
Connection of
outdoor unit
from other line
E20
E20
02:
Connection of
indoor unit from
other line
I/F
Comp.
Fa
n
O
01
O
02
E
3
1
E
3
1
O
O
03
Circle (O): Faulty IPDU
of
Description
System status
Duplicated
Stop of
master remote
corresponding
controller
unit
Indoor inter-
Stop of
MCU
corresponding
communication
unit
error
Automatic
All stop
address starting
error
Indoor unit not
All stop
found during
automatic
address setting
Too many
All stop
indoor units
connected
Error in
Stop of
communication
corresponding
between indoor
unit
header and
follower units
Connection to
All stop
other line found
during
automatic
address setting
IPDU
All stop
communication
error
96
119
Error detection
Check items (locations)
condition(s)
In two remote controller
Check remote controller
configuration (including
settings.
wireless), both controllers are
Check remote controller
set up as master. (Header
P.C. boards.
indoor unit is shut down with
alarm, while follower indoor
units continue operating.)
Communication cannot be
Check for defect in indoor
established / maintained
P.C. board.
upon turning on of power or
during communication.
Indoor automatic address
Perform automatic address
setting is started while
setting again after
automatic address setting for
disconnecting
equipment in other refrigerant
communication cable to
line is in progress.
that refrigerant line.
Indoor unit cannot be
Check connection of
detected after indoor
indoor-outdoor
automatic address setting is
communication line.
started.
Check for error in indoor
power supply system.
Check for noise from other
devices.
Check for power failure.
Check for defect in indoor
P.C. board.
Combined capacity of
Check capacities of indoor
indoor units exceeds
units connected.
130 % of combined
Check combined HP
capacity of outdoor units.
capacities of indoor units.
Check HP capacity
Note:
settings of outdoor units.
If this code comes up
Check No. of indoor units
after backup setting for
connected.
outdoor unit failure is
Check for defect in outdoor
performed, perform "No
P.C. board (I/F).
overloading detected"
setting.
<"No overloading detected"
setting method>
Turn on SW09 / Bit 2 on I/F
P.C. board of outdoor unit.
More than 13 indoor units
are connected.
Periodic communication
Check remote controller
between indoor header and
wiring.
follower units cannot be
Check indoor power supply
maintained.
wiring.
Check P.C. boards of
indoor units.
Equipment from other line is
Disconnect inter-line tie
found to have been
cable in accordance with
connected when indoor
automatic address setting
automatic address setting is
method explained in
in progress.
"Address setting" section.
Communication is disrupted
Check wiring and
between IPDUs (P.C.
connectors involved in
boards) in inverter box.
communication between
IPDU-I/F P.C. board for
bad contact or broken wire.
Check for defect in outdoor
P.C. board (I/F, IPDU).
Check for external noise.