Toshiba MCY-MHP0305HT-C Service Manual page 59

Air-conditioner (multi type)
Table of Contents

Advertisement

2
Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the
addresses. About one minute after turning on the power, confirm that the 7-segment display on
the outdoor unit indicates "U.1. - - -" and operate the interface P.C. board on the outdoor unit of
the refrigerant line as follows.
S
W
0
1
S
W
0
2
S
W
0
3
Confirm that the 7-segment display indicates
2
1
2
"A.d.buS" and turn SW04 ON for more than five
seconds.
Confirm that the 7-segment display indicates
2
2
2
"A.d.nEt" and turn SW04 ON for more than five
seconds.
3
Confirm that the 7-segment display indicates "A.d. C.L." and set SW01, SW02 and SW03 to 1, 1, 1
respectively.
4
After a time "U.1.L08" appears on the 7-segment display if the address clearing has been
completed successfully.
If the 7-segment display indicates "A.d. n.G.", the outdoor unit may still connected with other
refrigerant lines. Check the connection of the relay connectors between [U1, U2] and [U3, U4].
NOTE
Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be
cleared.
5
Set the addresses again after finishing the clearance.
S
W
0
4
58
81
C
e l
a
a r
b
e l
a
d
d
e r
s
s
e
s