Note: When real time viewer is running in PC, then, data will be stored in computer
hard disk. This data can be archived later from Real time viewer itself from "Meas-
ured data" icon. This data is same as Paperless Recorder internal memory (Histor-
ical data)
In case if PC running round the clock like a server, then, there may be no need to
manually transfer historical data from Recorer to PC via Memory stick.
Note: Please read "Real time viewer" help file from software itself for all the fea-
tures available in Real time viewer software

8.2.14 Serial (RS232/422/485)

The procedure is similar to Ethernet. But need to set bank properly for Modbus
Serial

8.2.15 View Real time data from Multiple Recorders

Assume, one Recorder database already added in Ethernet, IP address
192.168.0.11
Target: Connect second Recorder, IP address 192.168.0.12 to the Real time
viewer
Connect both the Recorders and PC to Ethernet switch
Use "Ping" instruction at DOS promot and check communication between PC and
two Recorders. If no response, then check IP address at all the devices and also
Ethernet cables
If there is good response from Recorders from "Ping" instruction, then, open Real
time viewer
Click "Configuration data" icon
154