Interface Module. TYPICAL D-100 NETWORK INTERFACE MODULE The D-100 is a totalizing display module that provides a local indication of liquid, gas or steam flow rate and total data. It can also be configured with an optional network interface to communicate data to the building control network.
Page 6
Two auxiliary analog rate inputs: 4-20 mA One auxiliary totalizer input: pulse or contact closure 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Flow Display Manual 08/12 - 0634-7 Page 6...
The ONICON D-100 is delivered fully programmed and ready to use with a specific flow meter. The serial number of the flow meter and any other sensor used with this D-100 will be found on a label located inside the enclosure. Do not attempt to use the D-100 with any other flow meter or sensor.
Find an easily accessible location where wire connections can be made and meter readings can be taken from floor level. Mount the D-100 on a vibration free surface. Avoid locations such as the plenum of a fan coil, heat exchanger or any housing that may contain electric motors or other strong sources of electrical interference.
Do not drill additional holes in this enclosure. Doing so may damage the electronic circuitry contained within and will void all warranties. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Flow Display Manual 08-12 - 0634-7...
Make connections on the mother board, located inside the enclosure, at terminal strips T3 and T4. Do not exceed 4.5 in-lb (0.5 Nm) of torque when tightening. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Flow Display Manual 08/12 - 0634-7...
Shield connections are required for proper operation. Failure to use shielded cable or to properly terminate shield connections may result in erratic operation. Shields should be terminated in the D-100 at the terminals provided. The shield connection at the flow meter should be left unterminated.
Shield and earth connections are required for proper operation. Failure to use shielded cable or to connect earth to both the flow meter and D-100 may result in erratic operation. Shields should be terminated at the D-100 shield terminals and left unterminated at the flow meter.
Shield and earth connections are required for proper operation. Failure to use shielded cable or to connect earth to both the flow meter and D-100 may result in erratic operation. Shields should be terminated at the D-100 shield terminals and left unterminated at the flow meter.
Shield and earth connections are required for proper operation. Failure to use shielded cable or to connect earth to both the flow meter and D-100 may result in erratic operation. Shields should be terminated at the D-100 shield terminals and left unterminated at the flow meter.
Shield and earth connections are required for proper operation. Failure to use shielded cable or to connect earth to both the flow meter and D-100 may result in erratic operation. Shields should be terminated at the D-100 shield terminals and left unterminated at the flow meter.
D-100 at the terminals provided. The shield connection at the flow meter should be left unterminated. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Flow Display Manual 08/12 - 0634-7...
This register can be zeroed on demand via the network. Contact ONICON for more information. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Flow Display Manual 08-12 - 0634-7...
Analog output signal connections are made at T1 terminals 7 through 14. Do not exceed 4.5 in-lb (0.5 Nm) of torque, when tightening the terminals. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Flow Display Manual 08/12 - 0634-7...
If any unit or multiplier values are changed at the D-100, the analog output value(s) will also be changed. If you are unsure of the ramifications of any changes you are contemplating, please contact ONICON for assistance.
Shane Hamilton ONICON Incorporated certifies that the flow and temperature sensors provided with this Btu meter have been individually calibrated based on the application specific data provided above; using standards directly traceable to the U.S. National Institute of Standards and Technology (N.I.S.T.).
Ai4 will produce an output equal to 37.5% of their programmed full scale output. This test confirms the operation of the D-100 processor board input circuitry for Ai3 and Ai4. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Flow Display Manual 08-12 - 0634-7...
Page 29
D-100 PROCESSOR BOARD RESET TEMP TEST PROG MODE ENABLE DEVICE ADDRESS PROGRAM ENABLE SERIAL COMM 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Flow Display Manual 08/12 - 0634-7 Page...
Page 30
1 AMP 1/4 AMP 1/8 AMP 250 VOLT 250 VOLT 250 VOLT SLO-BLO SLO-BLO SLO-BLO 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Flow Display Manual 08/12 - 0634-7 Page...
Page 31
D-100 ANALOG OUTPUT BOARD FLOW DELTA T BTU RATE LO TEMP HI TEMP 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Flow Display Manual 08/12 - 0634-7 Page...
Page 32
D-100 ANALOG OUTPUT BOARD with 4 analog outputs 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Flow Display Manual 08/12 - 0634-7 Page...
Page 33
2. DELIVERY AND TITLE: All product shipments are F.O.B. shipping point and title passes to the Buyer at the time ONICON delivers the merchandise to the carrier. Risk of loss or damage to the product passes to the Buyer at the time ONICON delivers the product to the carrier. The Buyer immediately upon receipt should inspect all shipments, and should there be any evidence of damage or loss in transit, Buyer must file claims or tracers upon carrier.
ONICON D-100 BaCnet serial interface. TYPICAL D-100 FLOW DISPLAY The D-100 is a totalizing display module that provides a local indication of liquid, gas or steam flow rate and total data. It can also be provided with an optional BaCnet Ms/TP or BaCnet/IP serial interface to communicate data to the building control network.
Incoming and outgoing Rs485 cable shield wires should be connected together, but must not be connected to the display. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Display Module BACnet Installation and Operation Guide 04/12 - 0635-2...
ONICON assumes no responsibility for damage caused to the external equipment as a result of an improper installation. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Display Module BACnet Installation and Operation Guide 04/12 - 0635-2...
NOTe: BaCnet Ms/TP shown above. see appendix a-4 for BaCnet/IP auxiliary output board. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Display Module BACnet Installation and Operation Guide 04/12 - 0635-2...
Page 42
(see fig. 3). set the selector switch, s1 to sRC. The switch must be rated for at least 20ma at 20VDC. fig. 3 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Display Module BACnet Installation and Operation Guide 04/12 - 0635-2 Page 9...
Page 43
In either case, the switch must be rated for at least 20ma at 20 VDC. fig. 4 fig. 5 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Display Module BACnet Installation and Operation Guide 04/12 - 0635-2 Page 10...
The standard Baud rate settings are 9600, 19200, 38400 and 76800 Baud. If the Baud rate setting was not provided to ONICON, the D-100 will be configured to “auto” detect the Baud rate of the network. In this configuration, the display should detect and automatically adjust to the proper rate when it is connected to the network.
001 – 254. The device instance number can be any number from 0 – 4,194,303. Both addresses are entered via the D-100 user interface on the front panel of the display. The procedure for entering or changing either the MaC address or the device instance number is outlined in the table on the next page.
Page 46
The new addresses are saved and the PROGRaM pushbutton. display will revert to the RUN mode. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Display Module BACnet Installation and Operation Guide 04/12 - 0635-2 Page 13...
Remote User Interface main menu (shown on the next page) select option “I”, Change IP address. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Display Module BACnet Installation and Operation Guide 04/12 - 0635-2...
Page 48
IP address as shown below and press enter. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Display Module BACnet Installation and Operation Guide 04/12 - 0635-2...
Page 49
D-100 for the change to take effect. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Display Module BACnet Installation and Operation Guide 04/12 - 0635-2...
Remote User Interface main menu (shown below) select option “I”, Change IP address. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Display Module BACnet Installation and Operation Guide 04/12 - 0635-2...
Page 51
IP address settings menu (shown below) select option 3. enter the new gateway address as shown below and press enter. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Display Module BACnet Installation and Operation Guide 04/12 - 0635-2...
Page 52
D-100 for the change to take effect. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com D-100 Display Module BACnet Installation and Operation Guide 04/12 - 0635-2...