SECTION 4 - PRINTERS
CONTROL BOARD SWITCH SETTINGS
SW1-8
ON
SW2-1
ON
SW2-2
ON
SW2-3
OFF
SW2-4
OFF
SW2-5
ON
SW2-6
ON
SW2-7
ON
SW2-8
Not Used
If equipped with HIGH SPEED serial board:
CONTROL BOARD SWITCH SETTINGS
SW1
OFF
SW2
OFF
SW3
OFF
SW4
ON
SW5
Not Used
SW6
OFF
SW7
OFF
Pin 20 & Pin 11 Act As Busy Line

Weigh - Tronix Printer

IMP-24 MODEL 2600
SW1
- OFF 1200 Baud*
SW2
- ON
1200 Baud*
MODEL 1220
Configure Menu
Baud = 1200
Data Bits = 8
Stop Bits = 1
Hshake = Busy-Line
Cols = 32
Invert = No
Font = 5 X 8
Mag = None
Custom Menu
Auto Seq = No
Zero = 0
Pound Sign = #
_(Underscore)
Busy Invert = No
ONline/OFFline = Yes
Ext Ch Set = No
Print Ready = Yes
Set Clock = Not Used
Reset Seq = Not Used
98
(CONT'D)
SDD (-) Pin 11
1200 Baud*
1200 Baud*
1200 Baud*
DSR Active
Buffer Threshold 32 Bytes
Busy Signal 200ms
DTR Space After Power ON
(-) Low When Busy
1200 Baud*
1200 Baud*
1200 Baud*
No Parity

Seiko

DipSW 1-1 =
OFF Input-Serial
DipSW 1-2 =
ON
Printing Speed High
DipSW 1-3 =
ON
Auto Loading - ON
DipSW 1-4 =
OFF Auto Lf - OFF
DipSW 1-5 =
ON
Setting Command - Enable
DipSW 1-6 =
OFF Printing Density - 100%
DipSW 1-7 =
ON
Printing Density - 100%
DipSW 1-8 =
ON
Printing, Density - 100%
DipSW 2-1
ON
Printing Columns - 40
DipSW 2-2 =
ON
User Font Back-Up - ON
DipSW 2-3 =
ON
Character Select - Normal
DipSW 2-4 =
OFF Zero - Slash
International Character Set -
DipSW 2-5 =
ON
American
International Character Set -
DipSW 2-6 =
ON
American
International Character Set -
DipSW 2-7 =
ON
American
International Character Set -
DipSW 2-8 =
OFF
American
DipSW 3-1 =
ON
Data Length - 8 Bits
DipSW 3-2 =
ON
Parity Setting - No
DipSW 3-3 =
ON
Parity Condition - Odd
DipSW 3-4 =
ON
Busy Control - H/W Busy
DipSW 3-5 =
ON
Baud Rate Select - 1200*
DipSW 3-6 =
OFF Baud Rate Select - 1200*
DipSW 3-7 =
ON
Baud Rate Select - 1200*
DipSW 3-8 =
OFF Baud Rate Select - 1200*
*
Settings shown for 1200 Baud. Other Baud rates can be se-
lected. Refer to Printer manufacturer's manual supplied with
Printer.
CONTROL CENTER SETUP

Chiller ID

Access Level Required: OPERATOR
Using the COMMS screen, assign an Identification
number to the chiller. This number will appear at the
top of each report.
FORM 160.81-O1 (1020)