York ZJ150 Installation Manual
Hide thumbs Also See for ZJ150:
Table of Contents

Advertisement

R-410A
ZJ SERIES W/SIMPLICITY SE
6-1/2 - 12-1/2 Ton
60 Hertz
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Preceding Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Rigging And Handling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Side Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Power And Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Optional Electric Heat. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Optional Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Options/Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Optional Variable Air Volume (VAV). . . . . . . . . . . . . . . . . . . 34
Optional Hot Gas Bypass (HGBP) . . . . . . . . . . . . . . . . . . . . 36
Economizer Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Dry Bulb Changeover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Single Enthalpy Changeover . . . . . . . . . . . . . . . . . . . . . . . . 36
Dual Enthalpy Changeover . . . . . . . . . . . . . . . . . . . . . . . . . 37
1 ZJ078-150 Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2 Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 ZJ078-150 Unit Accessory Weights . . . . . . . . . . . . . . . . . . . 9
4 ZJ078-150 Unit Physical Dimensions . . . . . . . . . . . . . . . . 11
5 ZJ078-150 Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . 11
6 Side Duct Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7 Control Wire Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9 Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
10 Electric Heat Minimum Supply Air . . . . . . . . . . . . . . . . . . . 31
11 Gas Pipe Sizing - Capacity of Pipe . . . . . . . . . . . . . . . . . . 32
12 Gas Heat Minimum Supply Air . . . . . . . . . . . . . . . . . . . . . . 32
13 Simplicity SE Economizer Board Details . . . . . . . . . . . . . . 38
14 Supply Air Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
15 Altitude/Temperature Correction Factors . . . . . . . . . . . . . . 43
1 Unit Shipping Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Condenser Covering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Compressor Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
®
5 Unit 4 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . . 9
6 Unit 6 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7 Center of Gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
8 ZJ078-120 Physical Dimensions . . . . . . . . . . . . . . . . . . . . 10
9 ZJ150 Physical Dimensions . . . . . . . . . . . . . . . . . . . . . . . 11
10 ZJ078-150 Unit Bottom Duct Openings . . . . . . . . . . . . . . 13
11 ZJ078-150 Unit Electrical Entry . . . . . . . . . . . . . . . . . . . . . 14
12 ZJ078-120 Unit Side Duct Openings . . . . . . . . . . . . . . . . . 14
13 ZJ150 Unit Side Duct Openings . . . . . . . . . . . . . . . . . . . . 15
14 ZJ078-150 Unit Left Duct Opening . . . . . . . . . . . . . . . . . . 15
15 ZJ078-150 Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
16 ZJ078-150 Transition Roof Curb . . . . . . . . . . . . . . . . . . . . 16
17 Side Panels With Hole Plugs . . . . . . . . . . . . . . . . . . . . . . 17
18 Return Downflow Plenum With Panel . . . . . . . . . . . . . . . . 17
19 Discharge Panel In Place . . . . . . . . . . . . . . . . . . . . . . . . . 17

TABLE OF CONTENTS

Auto . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Free Cooling Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Power Exhaust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Air Balance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Checking Air Quantity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Cooling Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . 52
Cooling Operation Errors . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Electric Heating Sequence Of Operations . . . . . . . . . . . . . . 54
Electric Heat Operation Errors. . . . . . . . . . . . . . . . . . . . . . 55
Gas Heating Sequence Of Operations . . . . . . . . . . . . . . . . . 55
Gas Heating Operation Errors . . . . . . . . . . . . . . . . . . . . . . 56
Start-Up (Cooling) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Start-Up (Gas Heat) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Checking Gas Heat Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Charging The Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Control Board Navigation Components . . . . . . . . . . . . . . . . . . 60
Unit Control Board Navigation Examples: . . . . . . . . . . . . . . 61
Start-Up Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
LIST OF TABLES
18 RPM Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
19 Indoor Blower Specifications . . . . . . . . . . . . . . . . . . . . . . . 49
20 Power Exhaust Specifications . . . . . . . . . . . . . . . . . . . . . . 49
21 Motor Sheave Datum Diameters . . . . . . . . . . . . . . . . . . . . 51
22 Additional Static Resistance . . . . . . . . . . . . . . . . . . . . . . . . 52
23 Electric Heat Limit Setting . . . . . . . . . . . . . . . . . . . . . . . . . 55
24 Electric Heat Anticipator Setpoints . . . . . . . . . . . . . . . . . . . 55
25 Gas Heat Limit Control Settings . . . . . . . . . . . . . . . . . . . . . 57
26 Gas Heat Anticipator Setpoints . . . . . . . . . . . . . . . . . . . . . 57
27 Gas Rate Cubic Feet Per Hour . . . . . . . . . . . . . . . . . . . . . 59
28 Gas Heat Stages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
29 Simplicity SE UCB Details . . . . . . . . . . . . . . . . . . . . . . . . . 63
30 Ignition Control Flash Codes . . . . . . . . . . . . . . . . . . . . . . . 68
LIST OF FIGURES
21 Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Heat and All Units With VFD Option . . . . . . . . . . . . . . . . . 19
VFD Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
25 Side Entry Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
26 Bottom Entry Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . 33
27 Simplified VFD Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
28 SE-ECO1001-0 Economizer Controller . . . . . . . . . . . . . . . 39
29 Belt Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
30 Altitude/Temperature Correction Factors . . . . . . . . . . . . . 44
31 Dry Coil Delta P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
32 Typical Flame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
33 Typical Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
34 Unit Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
35 Typical Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
36 Unit Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ZJ150 and is the answer not in the manual?

Questions and answers

Walter Pershin
May 8, 2025

how do i reset a high pressure switch trip on the compressor of this unit?

1 comments:
Mr. Anderson
May 19, 2025

To reset the high pressure switch trip on the York ZJ150 compressor, you must reset the alarm causing the “High Pressure Switch 1 Lockout.” This lockout occurs if the high pressure switch (HPS1) trips three times within two hours. Once the issue is resolved and the alarm is manually reset, the compressor operation can resume.

This answer is automatically generated

Summary of Contents for York ZJ150

  • Page 1: Table Of Contents

    25 Side Entry Gas Piping ......32 9 ZJ150 Physical Dimensions ..... . . 11 26 Bottom Entry Gas Piping .
  • Page 2: General

    1183875-YIM-A-1014 General ® ® York Predator units are single package air conditioners with optional gas heating designed for outdoor installation on a Before performing service or maintenance operations on rooftop or slab and for non-residential use. These units can be unit, turn off main power switch to unit.
  • Page 3 If damage is evident, the extent of the Renewal Parts damage should be noted on the carrier’s freight bill. A separate ® Contact your local York parts distribution center for authorized request for inspection by the carrier’s agent should be made in replacement parts.
  • Page 4 078 = 6.5 Ton 090 = 7.5 Ton FDD (Fault Detecter Diagnostics) 102 = 8.5 Ton York Commercial Comfort System (YCCS) Rtu Controller 120 = 10.0 Ton 150 = 12.5 Ton Hot Gas Bypass (Standard on VAV, Optional on CV)
  • Page 5: Installation

    1183875-YIM-A-1014 Installation Remove the toolless doorknobs and instruction packet prior to installation. Installation Safety Information Condenser Read these instructions before continuing this appliance Coil External installation. This is an outdoor combination heating and cooling Protective unit. The installer must assure that these instructions are made Covering available to the consumer and with instructions to retain them for future reference.
  • Page 6: Unit Shipping Bracket

    Roof efficient operation curbs for transitioning from Compressor #1 access Side entry power York Sunline™ footprint to Toolless (high-efficiency compressor and control wiring the ZJ Series footprints door latch w/crankcase heater) knockouts...
  • Page 7: Location

    If a unit is to be installed on a roof curb other than a ® varnishes, hydrochloric acid, cements and glues, York roof curb, gasketing must be applied to all antistatic fabric softeners for clothes dryers, masonry surfaces that come in contact with the unit underside.
  • Page 8: Weights And Dimensions

    1183875-YIM-A-1014 Before lifting, make sure the unit weight is distributed equally on the rigging cables so it will lift evenly. Units may be moved or lifted with a forklift. Slotted openings in the base rails are provided for this purpose. LENGTH OF FORKS MUST BE A MINIMUM OF 60 INCHES.
  • Page 9: Zj078-150 Unit Accessory Weights

    1183875-YIM-A-1014 Table 3: ZJ078-150 Unit Accessory Weights Weight (lbs.) Unit Accessory Shipping Operating Economizer Power Exhaust Electric Heat Gas Heat Variable Frequency Drive 1. Weight given is for the maximum heater size available (54KW). 2. Weight given is for the maximum number of tube heat exchangers available (8 tube).
  • Page 10: Zj078-120 Physical Dimensions

    29.03 29.03 14.85 Ø 24.58 TYP. 4 PL. 15.23 See detail A for gas inlet 11 3/8 See detail B for drain location 21 3/16 LEFT 4 3/16 FRONT 27 5/16 Figure 9: ZJ150 Physical Dimensions Johnson Controls Unitary Products...
  • Page 11: Zj078-150 Unit Physical Dimensions

    50 3/4 30 3/16 24 3/16 17 3/16 6 3/16 ZJ120 50 3/4 30 3/16 24 3/16 17 3/16 6 3/16 ZJ150 50 3/4 119 1/2 30 3/16 24 3/16 17 3/16 6 3/16 Detail A 3.184 3.184 Gas Pipe Inlet Gas Pipe Inlet Ø...
  • Page 12 1183875-YIM-A-1014 32 11/16 6 13/16 6 13/16 SUPPLY RETURN 27 1/2 LEFT RIGHT 20 1/8 19 1/8 17 1/8 12 5/16 Bottom condensate drain 14 1/2 25 9/16 Bottom gas supply entry 16 3/8 18 1/16 FRONT TOP VIEW Bottom power, control and convenience outlet wiring entry 3X Ø...
  • Page 13: Zj078-150 Unit Bottom Duct Openings

    1183875-YIM-A-1014 Disconnect Swith Cover Power Entry Ø 2-1/2 Control Entry Ø 7/8 Power Entry Ø 2-1/2 Convenience Outlet Cover Convenience Outlet Power Entry Ø 7/8 FRONT Figure 11: ZJ078-150 Unit Electrical Entry 1 8 - 1 /4 D o t P l u g s Return Supply Air 2 - 3 1 /3 2...
  • Page 14: Side Duct Dimensions

    1183875-YIM-A-1014 Dot Plugs 18-1/4 5-5/32 2-7/8 31-5/8 Figure 13: ZJ150 Unit Side Duct Openings Table 6: Side Duct Dimensions Dimension (in.) Unit Model Number ZJ078 28 1/4 18 1/16 28 1/4 18 1/4 ZJ090 28 1/4 18 1/16 28 1/4...
  • Page 15: Ductwork

    1183875-YIM-A-1014 RIGHT 80-5/8 INSULATED DECK UNDER CONDENSER SECTION SUPPLY RETURN 2 TYP. 50-1/2 INSULATED DECK UNDER COMPRESSOR SECTION FRONT 8 or 14 Figure 15: ZJ078-150 Roof Curb 2 TYP 23 4 30-1/2 50-1/2 80-5/8 RETURN SUPPLY 76-5/8 59-1/4 FRONT RIGHT 64-1/4 Figure 16: ZJ078-150 Transition Roof Curb Ductwork...
  • Page 16: Side Panels

    1183875-YIM-A-1014 Duct Covers Units are shipped with the side duct openings covered and a covering over the bottom of the unit. For bottom duct application, no duct cover changes are necessary. For side duct application, remove the side duct covers and install over the bottom duct openings.
  • Page 17: Compressors

    A disconnect must be utilized for these units. Factory installed to protect roofing. disconnects are available. If installing a disconnect (field ® supplied or York International supplied accessory), refer to Procedures which risk oil leakage include, but are not limited to, Figure 4 for the recommended mounting location.
  • Page 18 1183875-YIM-A-1014 Avoid damage to internal components if drilling holes for When connecting electrical power and control wiring to disconnect mounting. the unit, water-proof connectors must be used so that water or moisture cannot be drawn into the unit during normal operation. The above water-proofing conditions NOTE: Since not all local codes allow the mounting of a will also apply when installing a field supplied disconnect disconnect on the unit, please confirm compliance with...
  • Page 19: Field Wiring Disconnect - Cooling Unit With/Without Electric Heat And All Units With Vfd Option

    1183875-YIM-A-1014 CONTACTOR 1M FACTORY OR FIELD GROUND SUPPLIED DISCONNECT THREE PHASE POWER SUPPLY Figure 23: Field Wiring Disconnect - Cooling Unit With Gas Heat Without VFD Option Johnson Controls Unitary Products...
  • Page 20: Control Wire Sizes

    1183875-YIM-A-1014 Thermostat Wiring (Not applicable to units with VFD) thermostat to the unit. Refer to Table 7 for control wire sizing and maximum length. The thermostat should be located on an inside wall approximately 56 inch above the floor where it will not be Table 7: Control Wire Sizes subject to drafts, sun exposure or heat from electrical fixtures or Wire Size...
  • Page 21: Electrical Data

    1183875-YIM-A-1014 Table 8: Electrical Data ZJ078-150 Standard Motor - Without Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ Pwr (Tons) (Amps) Size...
  • Page 22 1183875-YIM-A-1014 ZJ078-150 Standard Motor - Without Powered Convenience Outlet (Continued) OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ Pwr (Tons) (Amps) Size (Amps) (Amps) RLA LRA...
  • Page 23 1183875-YIM-A-1014 ZJ078-150 Hi Static Motor - Without Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ Pwr (Tons) (Amps) Size (Amps) (Amps) RLA LRA...
  • Page 24 1183875-YIM-A-1014 ZJ078-150 Hi Static Motor - Without Powered Convenience Outlet (Continued) OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ Pwr (Tons) (Amps) Size (Amps) (Amps)
  • Page 25 1183875-YIM-A-1014 ZJ078-150 Standard Motor - With Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ Pwr (Tons) (Amps) Size (Amps) (Amps) RLA LRA Model...
  • Page 26 1183875-YIM-A-1014 ZJ078-150 Standard Motor - With Powered Convenience Outlet (Continued) OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ Pwr (Tons) (Amps) Size (Amps) (Amps) RLA LRA...
  • Page 27 1183875-YIM-A-1014 ZJ078-150 Hi Static Motor - With Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ Pwr (Tons) (Amps) Size (Amps) (Amps) RLA LRA...
  • Page 28 1183875-YIM-A-1014 ZJ078-150 Hi Static Motor - With Powered Convenience Outlet (Continued) OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ Pwr (Tons) (Amps) Size (Amps) (Amps)
  • Page 29: Physical Data

    1183875-YIM-A-1014 Table 9: Physical Data ZJ078-150 Physical Data Models Component ZJ078 ZJ090 ZJ102 ZJ120 ZJ150 Nominal Tonnage 12.5 AHRI COOLING PERFORMANCE Gross Capacity @ AHRI A point (Btu) 80000 93000 106000 124000 154000 AHRI net capacity (Btu) 77000 90000 102000...
  • Page 30 1183875-YIM-A-1014 ZJ078-150 Physical Data (Continued) Models Component ZJ078 ZJ090 ZJ102 ZJ120 ZJ150 Nominal Tonnage 12.5 CONDENSER FAN DATA Quantity of fans Fan diameter (Inch) Type Prop Prop Prop Prop Prop Drive type Direct Direct Direct Direct Direct Quantity of motors Motor HP each No.
  • Page 31: Optional Electric Heat

    1183875-YIM-A-1014 Optional Electric Heat These CSA approved heaters are located within the central compartment of the unit with the heater elements extending in The factory-installed heaters are wired for single point power to the supply air chamber. supply. Power supply need only be brought into the single point Fuses are supplied, where required, by the factory.
  • Page 32: Gas Pipe Sizing - Capacity Of Pipe

    1183875-YIM-A-1014 Table 11: Gas Pipe Sizing - Capacity of Pipe Nominal Iron Pipe Size Length of Pipe (ft.) 3/4 in. 1 in. 1-1/4 in. 1050 OPTIONAL COIL GUARD SHOWN NOTE: Maximum capacity of pipe in cubic feet of gas per hour based upon a pressure drop of 0.3 inch W.C.
  • Page 33: Options/Accessories

    1183875-YIM-A-1014 A 1/8-inch NPT plugged tapping, accessible for test gage The proper pressure regulation. (Two-stage regulation is connection, must be installed immediately upstream of the recommended). gas supply connection to the unit. The pressure drop in the lines between regulators and After the gas connections have been completed, open the between the second stage regulator and the appliance.
  • Page 34: Optional Variable Air Volume (Vav)

    1183875-YIM-A-1014 Smoke Detectors Economizer The Economizer can be a factory installed option or a field installed accessory. If factory installed, refer to the instructions included with the outdoor air hood to complete the assembly. Field installed Economizer accessories include complete The use of duct smoke detectors have specific limitations instructions for installation.
  • Page 35 1183875-YIM-A-1014 the transducer to a static pressure tap (field supplied) in the supply duct located at a point where constant pressure is expected. To prevent an unstable signal due to air turbulence, there should be no obstructions, turns or VAV terminal boxes If the unit is operated with the manual bypass switch in up- or down-stream of the sensing tube location for at least a the LINE (BYPASS) position and there are VAV boxes...
  • Page 36: Optional Hot Gas Bypass (Hgbp)

    1183875-YIM-A-1014 vary greatly among manufacturers, horsepower ratings and connections. For VFD-ready units also equipped with gas/ voltage requirements. Keep in mind that drive manufacturers electric heat, a terminal block located in the unit's control box also require various minimum clearances to allow for adequate and connected to the VAV board's "VAV BOX"...
  • Page 37: Dual Enthalpy Changeover

    1183875-YIM-A-1014 Free cooling is no longer available if the outside air enthalpy Once a compressor output is turned ON, the economizer rises above the Economizer Outside Air Enthalpy Setpoint. dampers continue to modulate to control the supply air temperature to the Economizer Setpoint. Dual Enthalpy Changeover At no time will a compressor output be turned ON if the For dual enthalpy economizer operation, the outside air...
  • Page 38: Simplicity Se Economizer Board Details

    1183875-YIM-A-1014 Figure 28: SE-ECO1001-0 Economizer Controller Table 13: Simplicity SE Economizer Board Details Cover Label Description Function & Comments Directional orientation: viewed with the center text of the cover label upright ANALOG INPUTS Terminal at left on upper edge of economizer board 24 VAC common/0-10 VDC negative for Connects through circuit trace to 24V~ IN pin COM economizer actuator position feedback...
  • Page 39: Se-Eco1001-0 Economizer Controller

    1183875-YIM-A-1014 Table 13: Simplicity SE Economizer Board Details (Continued) Cover Label Description Function & Comments SA BUS Pin connections at left on upper edge of economizer board EconCtrlr parameter reports UCB-to-economizer board SA bus communication status. Negative of the SA BUS communication Common for SA BUS power and circuit to the UCB.
  • Page 40 1183875-YIM-A-1014 Table 13: Simplicity SE Economizer Board Details (Continued) Cover Label Description Function & Comments 24V~ IN Pin connections at right on upper edge of economizer board 24 VAC common connection to power the economizer board. 24 VAC transformer Common referenced to Connects through circuit traces to C/COM terminals and pins cabinet ground distributed on the economizer board.
  • Page 41: Supply Air Limitations

    1183875-YIM-A-1014 Table 13: Simplicity SE Economizer Board Details (Continued) Cover Label Description Function & Comments 24 VAC common/0-10 VDC negative for the air Connects through circuit trace to 24V~ IN pin COM monitoring station sensor 24 VAC hot supplied for the building pressure 24V~ Connects through circuit trace to 24V~ IN pin HOT sensor...
  • Page 42 1183875-YIM-A-1014 Belt Tension The tension on the belt should be adjusted as shown in Figure 29. Procedure for adjusting belt tension: 1. Loosen six nuts (top and bottom) A. 2. Adjust by turning (B). 3. Never loosen nuts (C). 4. Use belt tension checker to apply a perpendicular force to one belt at the midpoint of the span as shown.
  • Page 43: Altitude/Temperature Correction Factors

    1183875-YIM-A-1014 Table 15: Altitude/Temperature Correction Factors Altitude (Ft.) Temp. 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.729 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.715 1.019 0.982...
  • Page 44: Altitude/Temperature Correction Factors

    1183875-YIM-A-1014 Drive Selection Determine side or bottom supply duct Application. Determine desired airflow. Calculate or measure the amount of external static pressure. Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance table.
  • Page 45: Airflow Performance

    1183875-YIM-A-1014 Airflow Performance Table 16: Airflow Performance - Side Duct Application ZJ078 (6.5 Ton) Side Duct Available External Static Pressure - IWG Air Flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 1.5 HP &...
  • Page 46 1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications. 2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. 3. kW = BHP x 0.932. ZJ150 (12.5 Ton) Side Duct Available External Static Pressure - IWG Air Flow...
  • Page 47: Airflow Performance - Bottom Duct Application

    1183875-YIM-A-1014 Table 17: Airflow Performance - Bottom Duct Application ZJ078 (6.5 Ton) Bottom Duct Available External Static Pressure - IWG Air Flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 1.5 HP &...
  • Page 48: Rpm Selection

    1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications. 2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. 3. kW = BHP x 0.932. ZJ150 (12.5 Ton) Bottom Duct Available External Static Pressure - IWG Air Flow...
  • Page 49: Air Balance

    1183875-YIM-A-1014 Table 19: Indoor Blower Specifications Motor Motor Sheave Blower Sheave Size Model Belt Datum Dia. Datum Dia. (Tons) Eff. Frame Bore (in.) Model Bore (in.) Model (in.) (in.) 1-1/2 1725 1.15 2.6 - 3.6 1VL40 AK74 (6.5) 1725 1.15 3.6 - 4.6 1VM50 AK74...
  • Page 50 Determine the number of turns the variable motor sheave is open. ZJ078 ZJ090 0.45 ZJ102 ZJ120 ZJ150 0.35 0.25 0.15 0.05 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500 Airflow (CFM) Figure 31: Dry Coil Delta P...
  • Page 51: Motor Sheave Datum Diameters

    1183875-YIM-A-1014 Supply Air Drive Adjustment EXAMPLE A 12.5 ton unit was selected to deliver 4,000 CFM with a 3 HP motor, but the unit is delivering 3,800 CFM. The variable pitch motor sheave is set at 2 turns open. Before making any blower speed changes review the Use the equation to determine the required DD for the new installation for any installation errors, leaks or undesirable motor sheave,...
  • Page 52: Operation

    1183875-YIM-A-1014 Table 22: Additional Static Resistance Electric Heat kW Size Model Cooling Only Economizer 4” Filter (Tons) 1900 0.06 0.02 0.12 0.05 0.06 0.07 0.08 0.10 2100 0.07 0.02 0.13 0.06 0.07 0.08 0.09 0.11 2300 0.08 0.04 0.14 0.07 0.08 0.09 0.10...
  • Page 53 1183875-YIM-A-1014 duct static pressure reaches or exceeds the high-limit set-point Economizer With Single Enthalpy Sensor (default = 4.5"), then the supply fan motor will be shutdown. When the room thermostat calls for "first-stage" cooling, the low The Supply Air Temperature (SAT) is controlled by staging voltage control circuit from "R"...
  • Page 54: Cooling Operation Errors

    1183875-YIM-A-1014 Cooling Operation Errors the thermostat is calling for cooling, the UCB will operate in the low ambient mode. Each cooling system is monitored for operation outside of the intended parameters. Errors are handled as described below. All Low ambient mode operates the compressors in this manner: system errors override minimum run times for compressors.
  • Page 55: Electric Heat Operation Errors

    1183875-YIM-A-1014 Table 23: Electric Heat Limit Setting LIMIT HEATER UNIT (TONS) VOLTAGE SWITCH OPENS °F For units with VFD and electric heat, the speed of the indoor blower motor continues to be controlled by duct ZJ078, 090 static pressure via the VAV control board. (6.5, 7.5) If there are VAV boxes present in the duct system, the boxes must be driven to the full-open position using a...
  • Page 56: Gas Heating Operation Errors

    1183875-YIM-A-1014 When the thermostat calls for the first stage of heating, the low- Gas Heating Operation Errors voltage control circuit from “R” to “W1” is completed. A call for Lock-Out heat passes through the UCB to the Ignition Control Board (ICB).
  • Page 57: Start-Up (Cooling)

    Table 26: Gas Heat Anticipator Setpoints SETTING, AMPS ZJ102 ZJ120 0.65 Start-Up (Cooling) ZJ150 1. Roll-out = 300°F, Auxiliary Limit = 200°F. Prestart Check List The ICB monitors the Pressure and Roll-out switches of gas After installation has been completed: heat units.
  • Page 58: Start-Up (Gas Heat)

    1183875-YIM-A-1014 • If blower rotation is in the wrong direction. Refer to Post Start Checklist Phasing Section in general information section. After the entire control circuit has been energized and the Check blower drive belt tension. heating section is operating, make the following checks: Check the unit supply air (CFM).
  • Page 59: Gas Rate Cubic Feet Per Hour

    1183875-YIM-A-1014 Adjustment”. Be sure not to over-fire the furnace on NOTE: To find the Btu input, multiply the number of cubic feet Second stage. If in doubt, it is better to leave the Second of gas consumed per hour by the Btu content of the gas stage of the furnace slightly under-fired.
  • Page 60: Charging The Unit

    1183875-YIM-A-1014 Table 28: Gas Heat Stages 2nd Stage Input 1st Stage Input # of Burner Tubes HEAT EXCHANGER TUBE (100% Btuh) (60% Btuh) 120,000 72,000 180,000 108,000 240,000 144,000 SUPPLY PIPE BURNER BURNER FLAME Adjustment Of Temperature Rise (BLUE ONLY) BURNER BRACKET The temperature rise (the difference of temperature between the IGNITOR...
  • Page 61: Simplicity™ Se (Smart Equipment) Firmware Version 3. Basic

    1183875-YIM-A-1014 SIMPLICITY™ SE (SMART EQUIPMENT) FIRMWARE VE RSION 3. BASIC UNIT CONTROL BOARD NAVIGATION EXAMPLES: The following document details the navigation and viewing of navigate the basic status menu and how to change basic the LCD display screen equipped as a standard item on the configuration settings.
  • Page 62: Typical Flame

    1183875-YIM-A-1014 When the "Cancel" button is pressed multiple times to exit each menu level and the screen returns to the first "Status, Alarms" dis- play the next demonstration can begin. In this demonstration the information below steps through the "Commissioning" menu. Step 2- Once commission Step 1- Beginning at the status/alarm screen toggle the joystick down three times.
  • Page 63: Simplicity Se Ucb Details

    1183875-YIM-A-1014 THERMOSTAT WIRED HERE SD-24 Figure 34: Unit Control Board Table 29: Simplicity SE UCB Details Description Function & Comments Terminal Directional orientation: viewed with silkscreen labels upright Limit, 24 VAC power and shutdown connections from unit wiring harness at left on upper edge of UCB Monitored 24 VAC input through heat section limit If voltage is absent, indicating the heat section is over- LIMIT...
  • Page 64 1183875-YIM-A-1014 Table 29: Simplicity SE UCB Details (Continued) Description Function & Comments Terminal Thermostat connection strip on left edge of UCB 1st stage heating request, 24 VAC input switched Not effective for cooling-only units from R 2nd stage heating request, 24 VAC input switched Not effective for cooling-only units or units with single-stage from R heat sections...
  • Page 65: Unit Control Board

    1183875-YIM-A-1014 Table 29: Simplicity SE UCB Details (Continued) Description Function & Comments Input required for operation; 3.625 VDC reading RAT+ to RAT– Return Air Temperature sensor input from 10KΩ with open circuit. Used in return air enthalpy calculation. RAT+ @ 77°F, Type III negative temperature coefficient Substitutes for space temperature if no other space thermistor temperature input is present.
  • Page 66 1183875-YIM-A-1014 Table 29: Simplicity SE UCB Details (Continued) Description Function & Comments The VFD alarm contact switches from R within the unit wiring 24 VAC hot input from the normally open VFD VFDFLT harness. 24 VAC input results in unit shutdown and a “VFD alarm contact fault”...
  • Page 67 1183875-YIM-A-1014 Table 29: Simplicity SE UCB Details (Continued) Description Function & Comments HPS2 24 VAC hot out for refrigerant circuit 2 High Not effective for one stage compressor UCBs. Connects (right pin) Pressure Switch through circuit trace to the R terminal Not effective for one stage compressor UCBs.
  • Page 68: Ignition Control Flash Codes

    1183875-YIM-A-1014 Table 29: Simplicity SE UCB Details (Continued) Description Function & Comments 4-way Joystick for display menu navigation Item USB connector at right of UCB Used for backup, restoration, & copying of board parameters as Type A female Universal Serial Bus connector well as board software updating through a flash drive Optional communication sub-board at center of UCB Terminal FC BUS connections on left edge of the communication board...
  • Page 69: Start-Up Sheet

    Technical Services Department available. Therefore, some variation in the startup procedure will 5005 York Drive exist depending upon the products capacity, control system, Norman, OK 73069 options and accessories installed.
  • Page 70 1183875-YIM-A-1014 1034349-UCL-B-0814 SAFETY WARNINGS The inspections and recording of data outlined in this procedure are required for start-up of Johnson Controls/UPG's packaged Lethal voltages are present during some start-up products. Industry recognized safety standards and practices checks. Extreme caution must be used at all times. must be observed at all times.
  • Page 71: Condensate Drain

    1183875-YIM-A-1014 1034349-UCL-B-0814 REFERENCE General Inspection Completed See Notes Unit inspected for shipping, storage, or rigging damage Unit installed with proper clearances Unit installed within slope limitations Refrigeration system checked for gross leaks (presence of oil) Terminal screws and wiring connections checked for tightness Filters installed correctly and clean Economizer hoods installed in operating position Condensate drain trapped properly, refer to Installation Manual...
  • Page 72 1183875-YIM-A-1014 1034349-UCL-B-0814 Operating Measurements - Air Flow Fan operates with proper rotation ID Fans Exh. Fans Cond. Fans Pressure drop across dry evaporator coil (At maximum design CFM) External Static Pressure Return Static Pressure Supply Static Pressure Supply Air CFM Using Dry Coil Chart Final Adjusted Supply Air CFM 1.
  • Page 73 1183875-YIM-A-1014 1034349-UCL-B-0814 OPERATING MEASUREMENTS - COOLING Discharge Discharge Liquid Line Suction Suction Stage Subcooling Superheat Pressure Temp. Temp. Pressure Temp. First ° ° ° ° ° Second (if equipped) ° ° ° ° ° Third (if equipped) ° ° ° °...
  • Page 74: 1183875-Yim-A-1014

    ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ ________________________________________________________________________________________________________ Subject to change without notice. Printed in U.S.A. 1183875-YIM-A-1014 Copyright © 2014 by Johnson Controls, Inc. All rights reserved. Supersedes: 860614-YIM-D-0614 York International Corporation 5005 York Drive Norman, OK 73069...