Figure 35 - Sample Printout (Status) - York YR Manual

Rotary screw liquid chillers with optiview control center for electro-mechanical starter & solid state starter
Hide thumbs Also See for YR:
Table of Contents

Advertisement

SECTION 4 - PRINTERS
YORK UPDATE
CHILLER ID 0
(c) 1997 – 2001 YORK INTERNATIONAL CORPORATION
Mon 21 Jun 1999 1:26:51 PM
SYSTEM RUN
LEAVING CHILLED LIQUID CONTROL
[List all warnings presently active]
Controls C.MLM.05.02.102
Run Time 0 Days 2 Hr 59 Min
Operating Hours
Number Of Starts
Control Source
Evaporator
–––––––––––––––––––––––––––––––––––––––––––––––––––––
Leaving Chilled Active Setpoint
Chilled Liquid Pump
Chilled Liquid Flow Switch
Leaving Chilled Liquid Temperature
Return Chilled Liquid Temperature
Evaporator Pressure
Evaporator Saturation Temperature
Small Temperature Difference
Condenser
–––––––––––––––––––––––––––––––––––––––––––––––––––––
Condenser Liquid Pump
Condenser Liquid Flow Switch
Leaving Condenser Liquid Temperature
Return Condenser Liquid Temperature
Condenser Pressure
Condenser Saturation Temperature
Small Temperature Difference
Drop Leg Refrigerant Temperature
[If Drop Leg Sensor enabled]
Sub Cooling Temperature
[If Drop Leg Sensor enabled]
Compressor
–––––––––––––––––––––––––––––––––––––––––––––––––––––
Discharge Temperature
Discharge Pressure
Discharge Saturation Temperature
Discharge Superheat
Liquid Injector
Low Superheat Event
Low Superheat Run Time

FIGURE 35 - SAMPLE PRINTOUT (STATUS)

100
[Skip the following section if Hot Gas Bypass is not enabled] Hot Gas
––––––––––––––––––––––––––––––––––––––––––––––––––––––
Hot Gas Solenoid On
Oil Sump
––––––––––––––––––––––––––––––––––––––––––––––––––––––
Oil Pressure
Differential Oil Pressure
Differential Filter Pressure
Oil Supply Solenoid
[Skip the following section if Level Control is not enabled] Refrigerant
= 298 Hr
Level Control
= 106
––––––––––––––––––––––––––––––––––––––––––––––––––––––
= Local
Refrigerant Level Target
Refrigerant Level Position
Ramp Up Time Remaining
= 45.0°F
= Run
[Skip the following section if Motor Type is not EM]
= Closed
Electro-Mechanical Starter
= 50.0°F
–––––––––––––––––––––––––––––––––––––––––––––––––––––––
= 59.3°F
Motor Run = On % Full Load Amps
= 78.2 Psig
= 41.1°F
= 10.0 ~F
[Skip the following section if Motor Type is not Mod A SSS] Liquid-
Cooled Solid State Starter
––––––––––––––––––––––––––––––––––––––––––––––––––––––
Motor Run
% Full Load Amps
= Run
% Phase A Voltage
= Closed
Phase B Voltage
= 85.0°F
Phase C Voltage
= 94.9°F
Phase A Current
= 135.8 Psig
Phase B Current
= 71.7°F
Phase C Current
= -13.3°F
= 85.0°F
[Skip the following section if Motor Type is not Mod B SSS]
= 2.0°F
Liquid-Cooled Solid State Starter
––––––––––––––––––––––––––––––––––––––––––––––––––––––
Motor Run
% Full Load Amps
= 121.6°F
% Starter Model
= 135.7 Psig
KW Hours
= 120.6ºF
Input Power
= 1.0°F
Phase A Voltage
= Open
Phase B Voltage
= 6
Phase C Voltage
= 8 min
Phase A Current
Phase B Current
Phase C Current
Phase A Temperature
Phase B Temperature
Phase C Temperature
[If Ramp Up in effect]
FORM 160.81-O1 (1020)
ISSUE DATE 10/05/2020
= False
= 120.7 Psig
= 41.6 Psid
= 13.1 Psid
= On
= 80 %
= 35 %
= 15 Sec
= 94 %
= On
= 94
= 447 V
= 409 V
= 442 V
= 193 A
= 204 A
= 190 A
= On
= 94
= 33L
= 20723 KWH
= 145 KW
= 447 V
= 409 V
= 442 V
= 193 A
= 204 A
= 190 A
= 88 ~F
= 89 ~F
= 75 ~F