Installation Into A Masonry Fireplace; Prefabricated Metal Chimney - Quadra-Fire TREKKERI-MBK Installation Manual

Trekker insert pellet
Hide thumbs Also See for TREKKERI-MBK:
Table of Contents

Advertisement

Figure 12.1 - Using a saws-all, cut out the floor.
Keep sharp edge of
metal floor away from
power cord
Figure 12.2 - Place the insert into the factory-built firebox. Ensure
that the power cord can not be damaged by the sharp metal edge.
You may need to cut out a notch to accommodate the cord.
H. Installation into a Masonry Fireplace
All modifications that can be made to a Factory Built Fireplace
can be made to a Masonry Fireplace.
In addition DO NOT remove any brick or mortar from the
existing fireplace.
• Removing floor of fireplace must not weaken structure
of firebox or reduce protection for combustible
materials.
• Final approval of this installation type is contingent
upon the appropriate local authority having jurisdiction.
12
WARNING
I. Prefabricated Metal Chimney
The chimney can be new or existing, masonry or prefabricated
and must meet the following minimum requirements:
- Must be minimum 6 inch (152mm) inside diameter
of high temperature chimney listed to UL 103 HT
(2100°F) or ULC-S628.
- Must use components required by the manufacturer
for installation.
- Must
maintain
manufacturer for installation.
- Refer to manufacturers instructions for installation
- This insert is listed to ASTM E 1509-12 Standard
and is approved for installation into listed factory-built
zero clearance fireplaces listed to UL 127 conforming
to the following specifications and instructions:
- The original factory-built clearance fireplace chimney
cap must be re-installed after installing the approved
chimney liner meeting type UL 103 HT requirements
(2100°F) per UL 1777.
- If the chimney is not listed as meeting HT requirements,
or if the factory built fireplace was tested prior to 1998,
a full height listed chimney liner must be installed from
the appliance flue collar to the chimney top.
- The liner must be securely attached to the insert flue
collar and the chimney top.
- The air flow of the factory-built zero-clearance
fireplace system must not be altered. The flue liner
top support attachment must not reduce the air flow
for the existing air-cooled chimney system.
- No dilution air is allowed to enter the chimney.
1. Secure the fireplace damper in the open position. If this
cannot be accomplished, it will be necessary to remove
the damper.
2. Seal damper area of chimney around chimney connector
with a high temperature sealant or seal insert against the
face of the fireplace.
3. Both methods must be removable and replaceable for
cleaning and re-installation.
Risk of Fire!
Follow venting manufacturer's clearances
and instructions when installing venting
system.
NOTICE: In Canada when using a factory-built chimney it
must be safety listed, Type UL103 HT (2100°F) [1149°C]
CLASS "A" or conforming to CAN/ULC-S629M,
STANDARD FOR 650°C FACTORY-BUILT CHIMNEYS.
7082-153K
clearances
required
WARNING
by
the
01/21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Trekkeri-pmhTrekkeri-twl

Table of Contents