Device Tone & Ash Indication - EMS FireCellWDC Installation Manual

Wireless door control
Table of Contents

Advertisement

Device tone and ash indication
In addition to fault reporting at the control panel, the FireCell WDC has various beep
and ash sequences to indicate a number of conditions.
During device startup sequence / motor operation
Beep sequence
Low-Low-Low
High-High-Low
(repeated until
resolved)
High-High-High-
High-Low-Low-
Low-Low
None
During standard operation
Beep sequence
Low-Low-High
(repeated until the
plunger releases)
High-Low-Low-Low
(repeated until
resolved)
High-Low
(seven times, then
door releases)
* Additional noti cation will be reported at the control panel as an analogue value 4
fault - Tamper/ Input Fault (short or open circuit).
† Door closing can be as a result of many factors such as a fire condition, a loss of
communication or a battery critical condition. Refer to the control panel for details.
©2019 EMS Ltd. All rights reserved.
Flash sequence
None
Red-Red (on rst
two beeps only)
Red-Red-Red-Red
(on rst four beeps
only)
Red-Green
Flash sequence
Red (on low beeps
only)
Red (on rst
sequence only)
Red (on rst beep
in sequence only)
Indicative meaning
Startup complete
Motor operation fail*
Battery pack 2 fail
(non-serviceable part)
Battery pack 1 low /
incorrectly inserted
(2x C batteries)
Indicative meaning
Plunger fail
Battery pack 2 fail
(non-serviceable part)
Door is about to
close†
Page 13 of 16
Action required
None
Remove and re-insert
batteries
Remove and re-insert
batteries (If fault persists,
return to manufacturer)
Replace / remove and
re-insert batteries
(as appropriate)
Action required
Check for obstructions to
the plunger
Remove and re-insert
batteries (If fault persists,
return to manufacturer)
Move away from the
doorway
MK241 Iss 2 20/11/2019 AJM

Advertisement

Table of Contents
loading

Table of Contents