Download Print this page

EMS fusion FCX-532-001 Installation Manual

Loop module c/w remote aerial facility

Advertisement

Quick Links

Loop Module
Installation Guide
POWER
FAULT
ISOLATOR
ACTIVE
Step 1
Pre Installation
The Fusion Loop Module installation must conform to
!
applicable local installation codes and should only be
installed by a fully trained competent person.
The following points require consideration upon installation:
Loop Module location. Refer to the design drawings generated
from the radio survey.
Radio performance. Refer to step 3 to ensure the radio
performance is optimised.
Remote aerials. If using remote aerials with this product, refer
to the Remote Aerial Installation manual for more information.
A maximum of 5 Loop Modules can be connected per loop.
Step 3
Mounting Location Guidelines
To
ensure
optimum
range
performance
the Loop Module
is achieved, the following
should be considered:
Ensure the Loop Module is
not installed within 2m of
other
radio
or
electrical
equipment
(not
including
the Control Panel).
Ensure the Loop Modules
aerials
are
not
installed
within 0.6m of any metal
work.
Step 5
Prepare the Loop Module Back Box
Drill
the
required
cable
entry
points
where necessary.
= Do Not Use
= Available Cable
Entry Points
©2014 EMS Radio Fire & Security Systems Ltd. All rights reserved
F usion
F usion
Loop Module
the
2m
of
0.6m
Loop
POWER
Module
FAULT
FIRE
Control
Panel
Fire Alarm Control
Part No

Product Description

Fusion Loop Module
FCX-532-001
Fusion Loop Module c/w Remote Aerial Facility
FCX-532-002
Step 2
Loop Module Components
1
2
3
Item No
1
Part Description
4X Corner
covers
Step 4
PCB Removal
POWER
The internal PCB of the Loop Module can be removed to ensure that
FAULT
damage is not caused during installation.
Remove the central retaining screw prior to unclipping the PCB.
ISOLATE
WD
Step 6
Fit Loop Module Back Box to the Wall
Fit the Back Box
to the wall.
All five circled
fixing positions
are available for
use.
1/2
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE
4
2
3
4
4x Lid
1x Loop
1x Loop
Screws
Module Lid
Module PCB
BACK
LOOP IN
LOOP OUT
-
-
TSD077 Iss 3c 15/04/14
5
5
1x Loop Module
Back Box
0V
RX
TX
3V
AJM

Advertisement

loading

Summary of Contents for EMS fusion FCX-532-001

  • Page 1: Product Description

    All five circled fixing positions are available for use. = Do Not Use = Available Cable Entry Points ©2014 EMS Radio Fire & Security Systems Ltd. All rights reserved TSD077 Iss 3c 15/04/14...
  • Page 2 Power Requirements 17mA @24V DC European Union 1999/5/EC (R&TTE directive): directives Hereby EMS Radio Fire & Security Systems declares that this device is in IP Rating IP54 compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC. Operating...

This manual is also suitable for:

Fusion fcx-532-002