Operating functions
Installer settings
- To open the installer settings, press
at the same time for 10 seconds.
- When menu is open, press
- Press
to confirm the settings.
- Press
to close the menu.
Parameters
Off-peak signal type
When you use off-peak time clock control, first determine
the type of signals,Only allow professional installers to operate.
- NO corresponds to Normally Open Signal.
,
- NC corresponds to Normally Close Signal.
Off-peak logic type
- In two ways using heat pump,should set in the installer
settings
-01 manually set off-peak time;
,
-02 switch signals by power companies.
Avoid Legionella
- This parameter is used to activate the legionella protection
mode.
,
- Once every 7 days, all domestic hot water is heated to 65℃.
Compressor maximum continuous working time
- If the maximum continuous working time of the compressor
-
more than Set Time, start auxiliary power.
Auxiliary Heating in off-peak time
- ON corresponds to turned on uxiliary Heating.
- OF corresponds to turned off uxiliary Heating.
,
switch off the system, then press
or
to change the value of the settings.
Description
27
and
Factory
Adjustment
setting
range
NO
NO , NC
01 , 02
01
ON
ON , OF
8h
5-10h
ON
ON , OF