F - Electric cabling
Each CPVS is wired for a pre-determined voltage, i.e. 460 V.
NEVER OPERATE THE CPVS ON A VOLTAGE OTHER
THAN THAT SHOWN ON THE ELECTRIC CABINET.
The electric current supply to the CPVS must comply with the
following table :
Type of cable to be used :
Power cable size
(for a maximum 32.8 ft length)
CPVS Model
40
50
60
75
SAFETY REGULATIONS
It should be remembered that safety regulations require :
• An earth socket to be used.
• A manual isolating switch, cutting all three phases ; this switch
must be clearly visible near the CPVS unit.
• The electric current must be cut whenever maintenance work is
carried out on the machine (except for pressurized oil change)
the isolating switch (RK5 type)
CPVS Model
40
50
60
75
Chicago Pneumatic Compressors
62 305 258 65
VOLTAGE
460 V
AWG4
AWG3
AGW1
AWG0
Fuses to be used for
460 V
80
100
125
150
01/2008