13. OUTDOOR INSTALLATION
13-4. Countermeasure to wind
Referring to the figure shown below, take appropriate measures which will suit the actual situation of the place for installation.
A unit installed alone is vulnerable to strong winds. Select the installation site carefully to minimize the effect of winds.
To install a unit in a place where the wind always blows from the same direction, install the unit so that the outlet faces away
from the direction of the wind.
A
A
Wind
Install the outdoor unit where seasonal
winds do not blow directly against the
unit, such as behind a building.
13-5. Precautions for installing a panel heater
If there is a risk that the drain water will freeze inside the outdoor unit, the installation of a panel heater is recommended.
When installing a panel heater, provide sufficient space for maintenance accordingly.
For details, refer to the installation manual for the panel heater.
13-6. Caution on selecting outdoor units
Consult your dealer when the following issues on Y-Series are the key concern.
Warm air may flow out from the indoor unit during heating Thermo-OFF.
Refrigerant flow sound may occur in the rooms with low background noise such as hotel rooms, hospital rooms,
bedrooms, or conference rooms.
To avoid the above issues on Y-Series, changing board settings on the indoor and outdoor units is required.
Ask AC&R Works for details.
MEES19K116
Install the outdoor unit to avoid having
A
seasonal winds against the front of air
outlet/inlet on the unit.
Y-Series