13. INSTALLATION

13-1. General requirements for installation
13. INSTALLATION
1. If possible, locate the unit to reduce the direct thermal radiation to the unit.
2. Consider the amount of noise the unit produces when choosing an installation location.
Valves and refrigerant flow on the outdoor/heat source unit may generate noise.
3. Avoid sites that may encounter strong winds.
4. Ensure the installation site can bear the weight of the unit.
5. Condensation should be moved away from the unit, particularly in heating mode.
6. Provide enough space for installation and service as shown in section 13-2. Spacing.
7. Avoid sites where acidic solutions or chemical sprays (such as sulfur sprays) are used frequently.
8. The unit should be provided from combustible gas, oil, steam, chemical gas like acidic solution, sulfur gas and so on.
13-2. Spacing
In case of single installation, 600mm or more of back space as front space makes easier access when servicing the unit
from rear side.
350(13-13/16)
MEES21K047
The space for
control box
replacement
Top view
Service space
(front side)
880(34-11/16)
600(23-5/8)
450(17-3/4)
Service space
The space for
(front side)
control box
replacement
WR2-Series-575V
Unit: mm (in.)
128