8. CAPACITY TABLES

8-3. Correction by total indoor

CITY MULTI system has different capacities and inputs when many combinations of indoor units with different total capacities are
connected. Using following tables, the maximum capacity can be found to ensure the system is installed with enough capacity for
a particular application.
PUHY-M200YNW-A1
kW
22.4
Cooling
Capacity
BTU/h
76,400
Input
kW
4.72
PUHY-M200YNW-A1
Heating
kW
25.0
Capacity
BTU/h
85,300
Input
kW
5.08
PUHY-EM200YNW-A1
kW
22.4
Cooling
Capacity
BTU/h
76,400
Input
kW
4.38
PUHY-EM200YNW-A1
kW
25.0
Heating
Capacity
BTU/h
85,300
Input
kW
4.94
PUHY-M250YNW-A1
kW
28.0
Cooling
Capacity
BTU/h
95,500
Input
kW
6.96
PUHY-M250YNW-A1
kW
31.5
Heating
Capacity
BTU/h
107,500
Input
kW
7.14
PUHY-EM250YNW-A1
kW
28.0
Cooling
Capacity
BTU/h
95,500
Input
kW
6.36
PUHY-EM250YNW-A1
kW
31.5
Heating
Capacity
BTU/h
107,500
Input
kW
6.92
MEES19K116
PUHY-(E)M200YNW-A1
1.2
1.0
0.8
0.6
0.4
0.2
1.2
1.0
0.8
0.6
0.4
0.2
50
100
PUHY-(E)M250YNW-A1
1.2
1.0
0.8
0.6
0.4
0.2
1.2
1.0
0.8
0.6
0.4
0.2
100
150
150
200
Total capacity of indoor units
200
250
Total capacity of indoor units
Y-Series
Cooling
Heating
250
300
Cooling
Heating
300
350
34