The total length of liquid pipe of each size is as follows:
ø9.52: A + B + C + D + a + b + e = 40 + 10 + 15 + 10 + 10 + 5 + 10 = 100 m
ø6.35: c + d = 10 + 10 = 20 m
A
a
M100
Total length of liquid
Additional
refrigerant charge
=
x 0.050 (kg/m)
(kg)
100 (m) x 0.050 (kg/m)
=
100 x 0.050
= 8.9 (8.88) kg
Amount of factory charged refrigerant
Outdoor unit
Charged amount
model
(E)M200
(E)M250
6.5kg
(E)M300
Maximum refrigerant charge
There is a limit to the amount of refrigerant that can be charged into a unit. Regardless of the amount yielded by the formula above, observe the maximum