Mitsubishi Electric CITY MULTI PUHY-M200-300YNW-A1 Data Book page 54

Air conditioning systems
Table of Contents

Advertisement

11. M-NET CONTROL
11-4-2. Rule of setting address
Unit
Indoor unit
System control interface
(MAC-333IF-E)
A-M converter
(PAC-SF83MA-E)
Air handling unit controller
(PAC-AH125, 140, 250, 500M-J)
CITY MULTI connection Kit
(PAC-LV11M-J)
Outdoor unit
BC controller
(Main)
BC controller
(Sub)
ME Remote
controller
(Main)
ME Remote
controller
(Sub)
ON/OFF remote
controller
AE-200E/AE-50E
AG-150A
EB-50GU-J
EW-50E
AT-50B
PAC-YG50ECA
BAC-HD150
LMAP04-E
PAC-YG60MCA
PAC-YG63MCA
PAC-YG66DCA
Lossnay, OA
processing unit
PAC-IF01AHC
Note1: To set the address to "100", set it to "50"
Note2: Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected. OC, OS1 and OS2 are ranked in descending
order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
MEES19K116
Address setting
Example
01 ~ 50
10
51 ~ 99, 100
(Note1)
10
52 ~ 99, 100
10
52 ~ 99, 100
10
1
101 ~ 150
Fixed
10
1
151 ~ 199, 200
Fixed
10
201 ~ 250
100
10
0,2
0~5
000, 201 ~ 250
100
10
0,2
0~5
000, 201 ~ 250
100
10
0,2
0~5
000, 201 ~ 250
100
10
2
201 ~ 250
Fixed
10
01 ~ 50
10
01 ~ 50
10
01 ~ 50
10
01 ~ 50
10
2
201 ~ 250
Fixed
10
Note
Use the most recent address within the same group of
indoor units. Make the indoor units address connected
to the BC controller (Sub) larger than the indoor units
address connected to the BC controller (Main).
If applicable, set the sub BC controllers in an PURY
system in the following order:
(1) Indoor unit to be connected to the BC controller (Main)
1
(2) Indoor unit to be connected to the BC controller (No.1 Sub)
(3) Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)
A maximum of 12 BC controllers are connectable.
The smallest address of indoor unit in same refrigerant
system + 50
Assign sequential address numbers to the outdoor
units in one refrigerant circuit system. OC, OS1 and
OS2 are automatically detected. (Note 2)
1
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
The address of outdoor unit + 1
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
1
as "01~ 50"
Lowest address within the indoor units connected to
the BC controller (Sub) plus 50.
1
The smallest address of indoor unit in the group + 100
The place of "100" is fixed to "1"
1
The address of main remote controller + 50
The address automatically becomes "200" if it is set
as "00"
1
The smallest group No. to be managed + 200
The smallest group No. to be managed is changeable.
1
0~9
AT-50B cannot be set to "000".
1
0~9
Settings are made on the initial screen of AG-150A.
1
0~9
Settings are made with setting tool of BM ADAPTER.
1
1
1
1
1
After setting the addresses of all the indoor units,
assign an arbitrary address.
1
1
Y-Series
52