Configuring; Return To Default Settings - Evikon PluraSens E2638 Series User Manual

Ethylene oxide detector-transmitter
Hide thumbs Also See for PluraSens E2638 Series:
Table of Contents

Advertisement

E2638-ETO
Configuring
A standard configuration kit includes a USB-RS485 converter, fixed flow regulator, gas
tubing with applicators, and a software pack. Please contact your Seller for more
information.
Detectors-transmitters E2638 share all functionalities of the PluraSens® multifunctional
platform. The features and options include:
Digital output change rate-limiting filter
Digital integrating (averaging) filter
Free assignment of each analog output to the chosen parameter
Flexible setting of analog output scales for each output
Output zero and slope adjustment for calibration
Free assignment of each of two relays to the chosen parameter
Several relay control logic modes
Switch delays and minimum on/off state durations for each relay
The output scales can be changed by Modbus commands by using the configuration
software and the standard configuration kit (see Modbus RTU Communication).

Return to default settings

To reset the device's Slave ID, baud rate, and stop bit numbers to factory settings, proceed
as follows:
1. De-energize the device
2. Connect the X6 jumper
3. Turn on the device
4. De-energize the device
5. Disconnect the X6 jumper
6. Turn on the device
14
Rev 10.03.2021