4| Compressor assembly

4.6 Pipe connections

Fig. 10: Stepped
internal diameters
ATTENTION Overheating can damage the valve.

4.7 Pipes

Pipes and system components must be clean and dry inside and free of scale, swarf and layers of
rust and phosphate. Only use air-tight parts.
Lay pipes correctly. Suitable vibration compensators must be provided to prevent pipes being cracked
and broken by severe vibrations.
Ensure a proper oil return.
Keep pressure losses to an absolute minimum.

4.8 Operating the shut-off valves

Before opening or closing the shut-off valve, release the valve spindle seal by approx. ¼ of a turn
counter-clockwise.
After activating the shut-off valve, re-tighten the adjustable valve spindle seal clockwise.
Valve spindle seal
Fig. 11
The pipe connections have stepped internal diameters so that pipes
with standard millimetre and inch dimensions can be used.
The connection diameters of the shut-off valves are designed for
maximum compressor output. The required pipe cross-section
must be matched to the capacity. The same applies for non-return
valves.
Therefore, remove the pipe supports from the valve before
soldering.
Solder only using inert gas to inhibit oxidation products (scale).
Fig. 12