Section 10: Installation Drawings; A0000293718 Rev B Page 1 Of 2 - Generac Power Systems Protector Series Installation Manuallines

Spark-ignited stationary generators
Hide thumbs Also See for Protector Series:
Table of Contents

Advertisement

Section 10: Installation Drawings

A0000293718 Rev B Page 1 of 2

WEIGHT DATA
WEIGHT
WEIGHT
ENCLOSURE
ENGINE/KW
GENSET ONLY
SHIPPING SKID
MATERIAL
KG [LBS]
KG [LBS]
4.5L/48KW
AL
808 [1781]
51 [112]
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
EXHAUST MUFFLER
ENCLOSED WITHIN
GENERATOR ENCLOSURE
RADIATOR/EXHAUST
DISCHARGE AIR
47
58
[1.8]
[2.3]
TYP
Installation Guidelines For Spark-Ignited Stationary Generators
SERVICE ITEM
SHIPPING WEIGHT
KG [LBS]
859 [1893]
OIL DRAIN HOSE
RADIATOR DRAIN HOSE
COOLANT RECOVERY BOTTLE RIGHT SIDE
AIR INTAKE
RADIATOR FILL CAP
(BOTH SIDES)
AIR CLEANER ELEMENT
REMOVE COVER
SPARK PLUGS
FOR ACCESS TO
RADIATOR FILL
CAP
REFERENCE OWNERS MANUAL
FOR PERIODIC REPLACEMENT
PARTS LIST
843 [33]
BATTERY 12V
CENTER OF GRAVITY
TOP VIEW
GROUP 27F
(SEE NOTE 5)
NEGATIVE GROUND
P/N G058665
CIRCUIT BREAKER
2026 [79.8] TYP
2119
[83.4]
OVERALL LENGTH
LEFT SIDE VIEW
4.5L
NOTES:
OIL FILL CAP
LEFT SIDE
OIL DIP STICK
LEFT SIDE
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE IS 6" OFFSET OF OVERALL LENGTH
OIL FILTER
LEFT SIDE
AND WIDTH OF GENERATOR. {1193.8 (47") WIDE X 2423.2 (95.4") LONG}. REFERENCE
INSTALLATION GUIDE SUPPLIED WITH THE UNIT FOR CONCRETE PAD GUIDELINES.
RIGHT SIDE
REFERENCE MANUFACTURER'S SPECIFICATIONS IF USING ENGINEERED, PREFABRICATED SLABS.
RIGHT SIDE
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
ROOF TOP
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
LEFT SIDE
STATE, AND LOCAL CODES.
LEFT SIDE
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
MUFFLER
SEE NOTE 11
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
DRIVE BELT
EITHER SIDE
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.
BATTERY
LEFT SIDE
4. REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS
THE STUB-UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES.
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
7. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
8. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
9. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC
SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS.
10. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE
AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED.
11. EXHAUST MUFFLER ENCLOSED WITHIN GENERATOR ENCLOSURE,
REMOVE FRONT PANEL TO ACCESS.
REAR ENCLOSURE
COVER PANEL
SEE NOTE 3
SEE NOTE 4
1168 [46.0]
OVERALL
HEIGHT
888 [35.0]
OVERALL WIDTH
CUSTOMER ACCESS
ASSEMBLY, CONTROL
REAR VIEW
PANEL ACCESS
BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
Installation Drawings
1212 [47.7]
DOOR TYP
65
[2.6]
FUEL LINE CONNECTION
318
1-1/4" NPT FEMALE TEE
[12.5]
THROUGH BASEFRAME OPENING
RIGHT SIDE VIEW
TITLE
VICE ACTION LATCH
ONE PER DOOR
ONE LIFT OFF DOOR PER
SIDE OF GENERATOR
53

Advertisement