Gaseous Fuel Systems
4. See
Table
4-3. Using both Minimum Operating
Temperature and Tank Vaporization Capacity col-
umns, find the BTU/hr vaporization rate of the gen-
erator at 100% load corresponding to the lowest
expected operating temperature.
5. See column 2, and note the Available Tank Capac-
ity. If it is greater than total run time fuel consump-
tion, see column 1 – this is the correct size tank
required. If it is less than total run time fuel con-
sumption, see next larger tank size. Verify lowest
operating temperature and tank vaporization
capacity.
24
Installation Guidelines For Spark-Ignited Stationary Generators