Instruction Leaflet IL16958
A200 Size 00, 0, 1 3 Pole Motor Controller
Figure 1. Size 1 A 200 Controller
THE CONTROLLER
The A200 motor controller, when wired as shown in Figure
6 or 7 , will operate as a full voltage starter and will give
protection against overload, but not against short circuit
currents, when wired and provided with overload relay (OlR)
heaters as listed in heater selection tables or when used
with any means of inherent protection activated by motor
temperature.
The controller should be protected against short circuits by
providing branch circuit protection not to exceed the maximum
protective device ratings listed in Table II.
This industrial type control is designed to be installed, perated,
and maintained by adequately trained work-men. These
instructions do not cover all details, variations, or combinations
of the equipment, its storage, delivery, installation, check out,
safe operation, or maintenance. Care must be exercised to
comply with local, state, and national regulations, as well as
safety practices, for this class of equipment.
Effective May 2011
Supersedes August 1992
Figure 2. Dimension Drawings (Dim. in inches)
AUXILIARY CONTACTS - TYPE J
One normally-open pole adjacent to the power poles is
supplied as the holding circuit auxiliary. A maximum of four
Type J auxiliary units can be installed in the recesses of
each contactor. These may be mounted with the terminals
in line with the power poles or may be mounted with the
terminals in a right angle relationship to the power poles.
Auxiliary contacts mount by means of a spring clip and
retainer screw.
Need help?
Do you have a question about the A200 and is the answer not in the manual?
Questions and answers