Control Unit; Functions And Operating Conditions In Weather-Compensated Mode - Viessmann VITODENS 050-W Installation And Service Instructions Manual

Wall mounted gas condensing boiler
Table of Contents

Advertisement

Functions and operating conditions in weather-compensated mode

If an outside temperature sensor is con-
nected to the control unit, the boiler
water temperature is regulated accord-
ing to the outside temperature.
In line with the selected heating curve,
a boiler water temperature is set for the
current outside temperature.
Heating curve for weather-compensated mode
90
80
70
60
50
40
30
20
20
15
Outside temperature in °C
X Indicator for selected heating curve
The setting can be made incre-
mentally between 5 and 35.
The heating curve is selected at the
control unit using a code. In the deliv-
ered condition, the heating curve with
code 20 is set.